Table 4-5 Assembly Object
Class Code:
0×04
OE2CIH
Instances:
#100 = Status Assembly
#101 = Status + Hart Ch 0,1 Assembly
#102 = Output Assembly
#110 = Build number
#225 = Configuration Assembly
Class Attributes:
None
Class Services:
None
Instance Attributes:
Attr
Name (Data Type)
Value
G/S Description
3
Data (STRUCT)
See following tables G/S See following tables
Instance Services:
Code
Service Name
Description
14 0×0E
Get Single
Read the assembly instance.
16 0×10
Set Single
Only for Instances 225 and 102
Channel Configuration Assembly
Table 4-6 Channel Configuration Assembly
Byte
Offset
Type
Name
Description
0×00
INT
Hart Pass-Through Hold Time
This is a module-wide parameter.
Individual channel configuration
follows.
0×02
INT
Padding
For structure alignment
0×04
INT
Config. Bits
(Chan 0)
Configuration bits. See table below.
0×06
INT
Fault Value
(Chan 0)
The value to use when the channel is in a
Fault state.
0×08
INT
Program Value
(Chan 0)
The value to use when the system is in
the Program state.
0×0A
INT
Low Engineering Value
(Chan 0)
Low Engineering units
0×0C
INT
High Engineering Value
(Chan 0)
High Engineering units
0×0E
INT
Low Clamp Value
(Chan 0)
User-defined value representing the
lowest output setting.
0×10
INT
High Clamp Value
(Chan 0)
User-defined value representing the
highest output setting.
0×12
INT
Padding
For structure alignment
0×14 to
0×23
-
Chan 1 Configuration
Same as Chan 0