Chapter 4
OE2CIH and HART
This chapter describes how to read and write HART data using the OE2CIH module. The
chapter includes the following sections:
HART features
Detecting HART devices
Auto scanning of HART dynamic variables
Supported HART CIP messages
Section 4.1
HART Features
The OE2CIH module functions as a HART master and communicates with HART
devices running HART revision 5 or greater. The OE2CIH module includes one HART
modem per channel to provide maximum acquisition speed and flexibility.
The HART transmitter and receiver conform to the HART Foundation’s physical layer
specification for a HART primary master. These specifications include AC P-P voltage
digital transmission bandwidth, analog signal bandwidth, wave shape, and a capacitive
drive.
The module performs the following HART operations:
Automatically reads the four dynamic HART variables; PV, SV, TV, and FV.
Automatically retrieves and stores HART device information, including
manufacturer’s ID device tag name, HART revision level, etc., and makes the
information available via a CIP unconnected message.
Automatically retrieves and stores extended device status using HART
Command 48. The extended status can be retrieved using an unconnected CIP
message.
Provides a HART pass-through interface using CIP unconnected messaging to
allow you or a remote client to send a HART command to a HART on any
channel.