C-4

Compact™ IO Isolated RTD/Resistance Module

User’s Manual Pub. 0300241-01 Rev. A

At this point you may click “Finish” to complete the configuration of your I/O module.
Configure each I/O module in this manner.

Section C.3
Configuring
I/O Modules

Once you have created a Generic Profile for 1769sc-IR6I Isolated RTD/resistance
module, you must enter configuration information into the tag database that is
automatically created from the Generic Profile information you entered. This
configuration information is downloaded to each module at program download, at power
up, and when an inhibited module is uninhibited.

First, enter the Controller Tag database by double-clicking on Controller Tags in the
upper portion of the Controller Organizer.

Based on the Generic Profile created earlier for 1769sc- IR6I module, the Controller Tags
screen looks like the following:

Tag addresses are automatically created for configured I/O modules. All local I/O
addresses are preceded by the word Local. These addresses have the following format:

Input Data: Local:s:I

Configuration Data: Local:s:C

Where s is the slot number assigned to the I/O modules in the Generic Profiles.

In order to configure an I/O module, you must open up the configuration tag for that
module by clicking on the plus sign to the left of its configuration tag in the Controller
Tag data base.