Compact™ IO Isolated RTD/Resistance Module

User’s Manual Pub. 0300241-01 Rev. A

4.2.4

Selecting Data Formats (Bits 12 through 14)

This selection configures channels 0 through 5 to present analog data in any of the
following formats:

Raw/Proportional Data

Engineering Units x 1

Engineering Units x 10

Scaled for PID

Percent Range

Table 4-3 (Channel Data Word Format)

Input

Type

Data Format

Engineering Units x 10

Engineering Units x 1

Scaled

For

PID

Proportional Counts

Percentage

˚ Celsius

˚ Fahrenheit

˚ Celsius

˚ Fahrenheit

Pt 385

-200 to +850

-328 to 1562

-2000 to +8500

-3280 to 15620

0 to 16383

-32767 to 32767

0 to 10000

Pt 3916

-200 to +630

-328 to 1166

-2000 to +6300

-3280 to 11660

0 to 16383

-32767 to 32767

0 to 10000

10 Cu 426

-100 to +260

-148 to 500

-1000 to +2600

-1480 to 5000

0 to 16383

-32767 to 32767

0 to 10000

100 Ni 618

-100 to +260

-148 to 500

-1000 to +2600

-1480 to 5000

0 to 16383

-32767 to 32727

0 to 10000

120 Ni 672

-80 to +260

-112 to 500

-800 to +2600

-1120 to 5000

0 to 16383

-32767 to 32767

0 to 10000

604 NiFe 518

-100 to +200

-148 to 392

-1000 to +2000

-1480 to 3920

0 to 16383

-32767 to 32767

0 to 10000

150 ohm

0 to +1500

5

0

to

+15000

5

0 to 16383

-32767 to 32767

0 to 10000

500 ohm

0 to +500

5

0

to

+5000

5

0 to 16383

-32767 to 32767

0 to 10000

1000 ohm

0 to +1000

5

0

to

+10000

5

0 to 16383

-32767 to 32767

0 to 10000

3000 ohm

0 to +3000

5

0

to

+30000

5

0 to 16383

-32767 to 32767

0 to 10000

Note: The engineering units data formats represent real engineering temperature
units provided by the module to the controller. The raw/proportional counts, scaled-
for-PID and percent of full-scale data formats may yield the highest effective
resolutions, but may also require that you convert channel data to real engineering
units in your control program.

Raw/Proportional Data

The value presented to the controller is proportional to the selected input and scaled into
the maximum data range allowed by the bit resolution of the A/D converter and filter
selected. The raw/proportional data format also provides the best resolution of all the
data formats.

If you select the raw/proportional data format for a channel, the data word will be a
number between -32767 and +32767. For example, if a Pt 385 RTD is selected, the

5

When resistances are selected, the temperature setting is ignored and the input data is the same for either °C or

°F selection.