4-4
Compact™ IO Isolated RTD/Resistance Module
User’s Manual Pub. 0300241-01 Rev. A
4.2.4
Selecting Data Formats (Bits 12 through 14)
This selection configures channels 0 through 5 to present analog data in any of the
following formats:
•
Raw/Proportional Data
•
Engineering Units x 1
•
Engineering Units x 10
•
Scaled for PID
•
Percent Range
Table 4-3 (Channel Data Word Format)
Input
Type
Data Format
Engineering Units x 10
Engineering Units x 1
Scaled
For
PID
Proportional Counts
Percentage
˚ Celsius
˚ Fahrenheit
˚ Celsius
˚ Fahrenheit
Pt 385
-200 to +850
-328 to 1562
-2000 to +8500
-3280 to 15620
0 to 16383
-32767 to 32767
0 to 10000
Pt 3916
-200 to +630
-328 to 1166
-2000 to +6300
-3280 to 11660
0 to 16383
-32767 to 32767
0 to 10000
10 Cu 426
-100 to +260
-148 to 500
-1000 to +2600
-1480 to 5000
0 to 16383
-32767 to 32767
0 to 10000
100 Ni 618
-100 to +260
-148 to 500
-1000 to +2600
-1480 to 5000
0 to 16383
-32767 to 32727
0 to 10000
120 Ni 672
-80 to +260
-112 to 500
-800 to +2600
-1120 to 5000
0 to 16383
-32767 to 32767
0 to 10000
604 NiFe 518
-100 to +200
-148 to 392
-1000 to +2000
-1480 to 3920
0 to 16383
-32767 to 32767
0 to 10000
150 ohm
0 to +1500
5
0
to
+15000
5
0 to 16383
-32767 to 32767
0 to 10000
500 ohm
0 to +500
5
0
to
+5000
5
0 to 16383
-32767 to 32767
0 to 10000
1000 ohm
0 to +1000
5
0
to
+10000
5
0 to 16383
-32767 to 32767
0 to 10000
3000 ohm
0 to +3000
5
0
to
+30000
5
0 to 16383
-32767 to 32767
0 to 10000
Note: The engineering units data formats represent real engineering temperature
units provided by the module to the controller. The raw/proportional counts, scaled-
for-PID and percent of full-scale data formats may yield the highest effective
resolutions, but may also require that you convert channel data to real engineering
units in your control program.
Raw/Proportional Data
The value presented to the controller is proportional to the selected input and scaled into
the maximum data range allowed by the bit resolution of the A/D converter and filter
selected. The raw/proportional data format also provides the best resolution of all the
data formats.
If you select the raw/proportional data format for a channel, the data word will be a
number between -32767 and +32767. For example, if a Pt 385 RTD is selected, the
5
When resistances are selected, the temperature setting is ignored and the input data is the same for either °C or
°F selection.