beautypg.com

1 rtd/resistance inputs and ranges, 2 data formats, 3 filter frequencies – Spectrum Controls 1769sc-IR6I User Manual

Page 10

background image

1-2

Compact™ IO Isolated RTD/Resistance Module

User’s Manual Pub. 0300241-01 Rev. A

1.1.1

RTD/Resistance Inputs and Ranges

The table below lists the RTD and resistance types and their associated full-scale ranges,
supported by the IR6I module.

Input Type

Input Range

˚ Celsius

˚ Fahrenheit

Pt 385

-200 to +850

-328 to 1562

Pt 3916

-200 to +630

-328 to 1166

10 Cu 426

-100 to +260

-148 to 500

100 Ni 618

-100 to +260

-148 to 500

120 Ni 672

-80 to +260

-112 to 500

604 NiFe 518

-100 to +200

-148 to 392

150 ohm

0 to +1500

1

500 ohm

0 to +500

1

1000 ohm

0 to +1000

1

3000 ohm

0 to +3000

1

1.1.2

Data Formats

The data can be configured on board each module as:

Engineering units x 1

Engineering units x 10

Scaled-for-PID

Percent of full-scale

Raw/proportional data

1.1.3

Filter Frequencies

The module uses a digital filter that provides high frequency noise rejection for the input
signals. The filter is programmable, allowing you to select from six different filter
frequencies for each channel:

4.17 Hz

10 Hz

16.7 Hz

19.6 Hz

62 Hz

470 Hz