Error Type

Hex

Equivalent

Module

Error

Code

(Binary)

Extended Error

Information Code

(Binary)

Error Description

X414

010

0 0001 0100

An unused bit has been set for ch1 (C:e.1)

X415

010

0 0001 0101

An unused bit has been set for ch2 (C:e.2)

X416

010

0 0001 0110

An unused bit has been set for ch3 (C:e.3)

X417

010

0 0001 0111

An unused bit has been set for ch4 (C:e.4)

X418

010

0 0001 1000

An unused bit has been set for ch5 (C:e.5)

X419

010

0 0001 1001

An unused bit has been set for Module Configuration Register
(C:e.6)