Chapter 3: Installation and Wiring

3-5

User’s Manual Pub. 0300241-01 Rev. A

right-side adjacent module’s bus lever is in the unlocked (fully right) position.

3)

Use the upper and lower tongue-and-groove slots (1) to secure the modules
together (or to a controller).

4)

Move the module back along the tongue-and-groove slots until the bus
connectors (2) line up with each other.

5)

Push the bus lever back slightly to clear the positioning tab (3). Use your fingers
or a small screwdriver.

6)

To allow communication between the controller and module, move the bus lever
fully to the left (4) until it clicks. Ensure it is locked firmly in place.

When attaching I/O modules, it is very important that the bus
connectors are securely locked together to ensure proper electrical
connection.

7)

Attach an end cap terminator (5) to the last module in the system by using the
tongue-and-groove slots as before.

8)

Lock the end cap bus terminator (6).

A 1769-ECR or 1769-ECL right or left end cap respectively must be
used to terminate the end of the bus.

Section 3.5

Mounting

During panel or DIN rail mounting of all devices, be sure that all debris
(metal chips, wire strands, etc.) is kept from falling into the module.
Debris that falls into the module could cause damage at power up.

3.5.1

Minimum Spacing

Maintain spacing from enclosure walls, wireways, adjacent equipment, etc. Allow 50 mm
(2 in.) of space on all sides for adequate ventilation, as shown below:

!

Attention

!

Attention

!

Attention