beautypg.com

OPTI-UPS DS120KC33 User Manual

Page 51

background image

(1)Input power to low or no utility

Recover utility to within+/-20%

(2)Battery voltage decreases to low

voltage point

Unload to 10%~20% of load

(3)Ol-3320 detects circuit error

Replace ol-3320

(4)Ol-3302 detects circuit error

Replace ol-3302

(5)Ol-3300 feedbacks circuit error

Replace ol-3300

Battery is in low voltage

and UPS is about to be

shut down

(6)Error on ol-3300 program

parameter

Correct program parameter

(1)No battery

Add battery

(2)Battery power is not insufficient Recharge

battery

(3)Ol-3302 detects circuit error

Replace ol-3302

Error on battery test

(4)Ol-3300 program parameter

inaccuracy

Correct program parameter

(1)Emergency switch functions

Recover Emergency Switch

(2)Input short circuit

Eliminate short circuit

(3)Ol-3304 detects circuit error

Replace ol-3304

Emergency power

functions

(4)Ol-3300 detects circuit error

Replace ol-3300