8-3 Simple troubleshooting for system function

Error message displayed

Description

Troubleshooting

(1)No battery found

Add battery

(2)Battery power is insufficient

Recharge battery

(3)Ol-3302 detects circuit error

Replace ol-3302

Battery can’t supply

power

(4)Ol-3300 program parameter

inaccuracy

Correct program parameter

(1)Utility voltage is too low

Recover utility to within+/-20%

(2)Ol-3320 detects circuit error

Replace ol-3320

(3)Ol-3300 feedbacks circuit error Replace ol-3300

Input voltage is lower

than 25%

(4)Ol-3300 program parameter

inaccuracy

Correct program parameter

(1)Error on system

Inform service technician

(2)Error on ol-3300 feedback circuit

Replace ol-3300

Temperature of main

machine is overheat

(3)Ol-3300 program parameter is too

high

Correct program parameter

Humidity of main

machine is too high

There is no this function for now

(1)No second power

Add second Power

(2)Ol-3320 detects circuit error

Replace ol-3320

(3)Ol-3300 feedbacks circuit error

Replace ol-3300

No second power found

(4)Ol-3300program parameter

inaccuracy

Correct program parameter

(1)No any power is added

Add any Power

(2)Error on ol-3320 detecting circuit

error

Replace ol-3320

(3)Error on ol-3302 detecting circuit

Replace ol-3302

(4)Error on ol-3300 feedback

Replace ol-3300

No any Power

(5)Error on ol-3300program

parameter

Correct program parameter

(1)Input power is too low or no utility Recover utility to within+/-20%

(2)Ol-3320 detects circuit error

Replace ol-3320

(3)Ol-3302 detects circuit error

Replace ol-3302

(4)Ol-3300 feedbacks circuit error

Replace ol-3300

Input voltage is too low

and battery discharges

(5)Error on ol-3300program

parameter

Correct program parameter

This manual is related to the following products: