Table 4-2-2A

For wire diameters for different capacity of UPS system, please check the table 4-2-2B below

Wire diameter of ground wire

10KVA 8mm

2

15KVA 8mm

2

22.5KVA 8mm

2

30KVA 14mm

2

45KVA 22mm

2

60KVA 22mm

2

80KVA 38mm

2

100KVA 38mm

2

120KVA 38mm

2

Table 4-2-2B