IQ+ OP-LIT 9/08
Instance ID 2 (position control)
NOTE:
There is no subclass
for instance 2
TAbLE 8.11.2 – S-SINGLE STAGE CONTROLLER ObJECT ATTRIbUTES; INSTANCE 2
attrIBute Id
hex
ServIce Id
HEx
name
Format
value
3
0E (get) 10 (set)
Data type
USINT
C3h = INT (default)
CAh = Real
4
0E (get) 10 (set)
Data units
UINT
1001h = Counts (default
1007h = Percent
1703h = Degrees
5
0E (get) 10 (set)
Control Mode
USINT
See table 8.11.3
6
10 (set)
Setpoint
UINT
Specified by data type
7
0E (get)
Process
variable
(Position)
Specified by
data type
Analog output value
Linked to S-Analog Sensor
Object, instance 3
9
OE (get) 10 (set)
Control
variable
Specified by S-
Analog Actuator
Object data type
Drive signal output
Linked to S-Analog
Actuator Object, instance 1
0000h - 7FFFh
0A
0E (get)
Status
BYTE
See table 8.11.4
11
OE (get) 10 (set)
Safe State
USINT
See table 8.11.5
TAbLE 8.11.4 – S-SINGLE
STAGE CONTROLLER ObJECT
STATUS bITmAP
BIt
deFInItIon
0
Alarm exception
0 = cleared, 1 = set
1
Warning exception
0 = cleared, 1 = set
2-7
Reserved
8.11 - S-Single Stage Controller Object
(continued)
TAbLE 8.11.3 – S-STAGE CONTROLLER
ObJECT CONTROL mODE vALUE
attrIBute
value
State
0
Normal
1
Closed
2
Open
3
Hold
4
Safe State (Closed)
5-63
Reserved
TAbLE 8.11.5 – S-SINGLE STAGE
CONTROLLER ObJECT SAFE STATE vALUE
attrIBute
value
State
0
Closed
1
Open
2
Hold (Default)
3
Safe Value - Closed
4-63
Reserved