6.0 - RS-232 Serial Interface and Commands
Interface basics
All IQ+ controllers support RS-232 serial communications available though auxiliary port. A full description of the communications protocol and a listing of all
active serial commands follows in this section. A three-wire connection needs to be completed to provide the communications lines, with Rxd (data from the
IQ+), Txd (data to the IQ+) as well as signal common on. See Section 3.0 for details.
NOTE:
Hardware handshaking is not available.
NOTE:
The default factory RS-232 communications parameter settings are 9600 Baud, 1 stop bit, no parity and 8-bit character.
These settings can only be changed using a serial command.
Every serial input command sent by the HOST has an end-of-line delimiter, carriage return ASCII 0x0D [hex], or the line feed character ASCII 0x0A [hex],
or the carriage return and line feed character in that order. The IQ+-device end-of-line delimiter is the carriage return and line feed characters.
Serial Commands Summary
Table 6.1 and 6.2 summarize the serial commands and responses available with the IQ+ controller. Additional commands
may be included to enable customer specific functions. Please contact Nor-Cal Products Intellisys Customer Support for more details.
TAbLE 6.1 – RS-232 SERIAL COmmANDS
SerIal
command
deScrIPtIon
noteS /
examPleS
C
Close the valve
Same function as pressing the CLOSE button
O
Open the valve
Same function as pressing the OPEN button
H
Hold the valve in the current position
Stops active pressure control, if device is in that mode
T1x
Sets the type of set point #1. When x=0, the set-point type is position.
When x=1, the set-point type is pressure.
S1xx.xx
Used to program a value for set point xx.xx is any number between 0.00 and
100.00, representing the % of gauge full scale
S150, for example, programs the value of 50% for the setpoint. When using
a 1 Torr gauge, this corresponds to 500 mTorr..
D1
Activates set-point #1.
Put the device in control mode, effectively making the setpoint active.
Vxx.xx
Go to valve position
xx.xx is 0 to 100% of full open
L0
Auto select CDG1 or CDG2 for best resolution
Default two gauge configuration.
L1
Control to and report CDG1 values only
Selects Gauge 1 for manitenance function.
L2
Control to and report CDG2 values only
Selects Gauge 2 for manitenance function.
N1xx
Sets the full scale range of CDG1
Values for xx can be found in Table 6.3
N2xx
Sets the full scale range of CDG2
Values for xx can be found in Table 6.3
J4
Clears the “initialization safety lock feature” included on some TPV and TSS
controllers
Initializes Valve
RS-232 Commands Examples
The following section provides examples of the most commonly used commands and responses. The serial command protocol is not case sensitive, though all
the command examples in this section are listed in capital letters. Furthermore, whenever necessary the character Ø has been used to designate the number
zero, so as to not confuse it with the letter O.
TAbLE 6.2 – RS-232 SERIAL REQUESTS AND RESPONSES
SerIal
requeSt
deScrIPtIon
reSPonSe
R1
Requests the set point value
S1+xxxx, where xxxx is a number from 0.00 to 100.00
R5
Requests the current pressure
P+xxxx, where xxxx is a number from 0.00 to 100.00
R6
Requests the current valve position
V+xxxx, where xxxx is a number from 0.00 to 100.00
R38
Requests the software version
IQ+3-[version #] [version date] (text)
R26
Report set point type
T1x, When x=0, the set-point type is position. When x=1, the set-point type
is pressure.
GSN
Get the serial number of the device
SN: xxxxxxxx
RN1
Requests full scale range of CDG1
N1xx.xx, where xx.xx is the full scale range of CDG1 in Torr
RN2
Requests full scale range of CDG2
N2xx.xx, where xx.xx is the full scale range of CDG2 in Torr
RESET
Resets the device
Same as cycling power