TAbLE 8.5.1
–
OUTPUT ASSEmbLy INSTANCES
InStance
hex
Byte
varIaBleS
ePath
hex
7 (default)
0-1
2-3
Control setpoint
Control instance
20 04 24 07 30 03
17
0-3
4-5
FP - Control setpoint
Control instance
20 04 24 17 30 03
97
(Master Slave)
0
1-2
3-4
5
6
7
Control mode
Pressure setpoint
Position setpoint
Control instance
Individual valve control (address)
Individual valve control (action)
20 04 24 97 30 03
8.5 - I/O Assembly Instances
The control instance indicates the significance of the control
setpoint:
1
= pressure control
2
= position control.
Note:
The process variable will be based on the full scale
range of the active sensor except for instance 96 hex
and instance 98 hex, where it is based on the full scale
range of each individual sensor. The active sensor can
be determined from attribute 5F hex, Active instance
number, of the S-Analog Sensor Object, class instance 0.
Note:
After establishing an I/O connection, data types of appli-
cation objects related to attributes included in the I/O assem-
blies will self-adjust to give consistency in data type between
pressure related and position related attributes. This applies
to attributes of the S-Analog Sensor Object, the S-Analog
Actuator Object and the
S-Single Stage Controller Object
Note:
Assembly instances 97 hex and 98 hex are
described in detail in the Master/Slave Object section.
TAbLE 8.5.2
– I
NPUT ASSEmbLy INSTANCES
InStance
hex
Byte
varIaBleS
ePath
hex
2
(default)
0
1-2
Exception status
Process variable
20 04 24 07 30 03
4
0
1-2
3-4
Exception status
Process variable
Control setpoint
20 04 24 04 30 03
5
0
1-2
3-4
5-6
Exception status
Process variable
Control setpoint
Valve position
20 04 24 05 30 03
0B
0
1-2
3-4
Exception status
Process variable
Valve
20 04 24 0B 30 03
5
Discrete
input 2
Discrete
Input 1
12
0
1-4
Exception status
FP - Process variable
20 04 24 12 30 03
1A
0
1-4
5-8
Exception status
FP - Process variable
FP - Valve
20 04 24 1A 30 03
9
Discrete
input 2
Discrete
Input 1
96
0
1-2
3-4
5-6
7
Exception status
Process variable input 1 (low range)
Process variable input 2 (high range)
Valve
Active process input instance
20 04 24 96 30 03
8
Discrete
input 2
Discrete
Input 1
98
(Master/Slave)
0
1-2
3-4
5-6
7
8
...
8 +
nn
Exception Status
Process variable input 1 (low range)
Process variable input 2 (high range)
Valve
Device Status
Cluster information (address 00 - Master)
...
Cluster information (address
nn
–
Slave nn)
20 04 24 98 30 03