beautypg.com

Operation, Testing & maintenance, Wiring the a.c. input – IOTA I-232 User Manual

Page 3: Labels, Completing installation

background image

Page 3

5. WIRING THE A.C. INPUT

A. The

I-232 and A.C. ballast must be on the same branch circuit.

B. The

I-232 requires an unswitched A.C. power source of either 120 or 277 volts. Select the proper voltage lead

and cap the unused lead.

C. When the

I-232 is used with a switched fixture, the A.C. input to the I-232 must be connected ahead of the

fixture switch. Refer to Illustration 3 for switched and unswitched fixture wiring diagrams.

BLACK

A.C. BALLAST

HOT A.C. LINE

WHITE

WHITE

(120V) BLK

(277V) ORG

TEST SWITCH

COMMON

BLK/ORG

BLK/ORG

BLACK

A.C. BALLAST

HOT A.C. LINE

WHITE

WHITE

(120V) BLK

(277V) ORG

TEST SWITCH

COMMON

Select proper voltage lead. Cap unused lead.

BLK/ORG

BLK/ORG

WALL

SWITCH

1

2

2

Use either BLK/ORG lead for wiring to common.

2

1

Select proper voltage lead. Cap unused lead.
Use either BLK/ORG lead for wiring to common.

2

1

1

2

2

Illustration 3

Switched Fixture

Unswitched Fixture

I-232

I-232

6. LABELS

Attach the appropriate labels adjacent to the

Test Switch and Charge Indicator. Annotate Re-lamping label for

lamp type and wattage. The Caution and the Re-lamping labels must be on the fixture in a readily visible location
to anyone attempting to service the fixture.

7. COMPLETING INSTALLATION

When the installation is complete, switch the A.C. power on and join the

I-232 unit connector.

OPERATION

Normal Mode – A.C. power is present. The A.C. ballast operates the fluorescent lamp(s) as intended. The I-232 is
in the standby charging mode. The

Charge Indicator will be lit providing a visual indication that the battery is being

charged.

Emergency Mode – The A.C. power fails. The I-232 senses the A.C. power failure and automatically switches to the
Emergency Mode. Two lamps are illuminated, at reduced output, for a minimum of 90 minutes. When the A.C. power
is restored, the

I-232 switches the system back to the Normal Mode and resumes battery charging. See page 1 of the

Instruction Manual.

TESTING & MAINTENANCE

Initial Testing – Allow the unit to charge approximately 1 hour, then conduct a short discharge test. Allow a 24 hour
charge before conducting a one hour test.
The

I-232 is a maintenance free unit, however, periodic inspection and testing is required. NFPA 101, Life Safety Code,

outlines the following schedule:
Monthly – Insure that the Charge Indicator light is illuminated. Conduct a 30 second discharge test by depressing the
Test Switch. Two lamps should operate at reduced output.
Annually – Insure that the Charge Indicator light is illuminated. Conduct a full 1

1

/

2

hour discharge test. The unit should

operate as intended for the duration of the test.

“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”

SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.

Consult Customer Service or visit www.iotaengineering.com for current warranty information.