IOTA I-40 User Manual
I-40, Instruction manual important safeguards, Read and follow all safety instructions
I-40
TBTS SERIES D
EMERGENCY
LIGHTING EQUIPMENT
INSTRUCTION MANUAL
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1.
CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
power is supplied to the unit.
2.
CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by discon-
necting the unit connector.
3.
CAUTION – This is a sealed unit. The integral, high temperature Ni-Cad battery is not replaceable. Replace
the entire unit when necessary and recycle or dispose of the nickel cadmium battery properly.
4.
DO NOT USE OUTDOORS - The I-40 is for use with grounded, UL Listed, damp location rated, indoor
fixtures. Not for use in heated air outlets or hazardous locations.
5. The
I-40 requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused
A.C. lead.
6. The
I-40 and A.C. ballast must be on the same branch circuit.
7. Do not mount near gas or electric heaters.
8. The
I-40 should be mounted in locations and at heights where it will not readily be subjected to tampering by
unauthorized personnel.
9. The
I-40 will cold strike and operate one 2´ through 4´ (20-40W) instant start, rapid start, U shape or circline,
T8 through T12 fluorescent lamps, including energy saving and long compacts for 90 minutes at reduced light
output.
10. The
I-40 is suitable for mounting in the ballast compartment or on top of the fixture. For top mount, order op-
tional mounting kit TMK-80. When used in conjunction with enclosed and gasketed fixtures, the
I-40 is suitable
for mounting in the ballast compartment only.
11. The
I-40 is compatible with all A.C. magnetic and electronic ballasts including multiple lamp ballasts with one
lamp operating in the emergency mode.
12. Suitable for use in damp locations and in enclosed and gasketed fixtures.
13. For use in 0° C minimum, 50° C maximum ambient temperatures.
14. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
15. Do not use this equipment for other than intended use.
16. Install in accordance with the National Electrical Code and local regulations.
17. Installation and servicing should be performed by qualified personnel.
18. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before
final installation.
SAVE THESE INSTRUCTIONS