Page 2

7/8" BUSHING

FIXTURE

BALLAST CHANNEL COVER

PLASTIC TUBE

CHARGE INDICATOR
LIGHT

FIXTURE LENS

INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off and the I-232 unit connector is disconnected.

1. MOUNTING THE I-232

Remove the ballast channel cover. For heat consideration, mount the

I-232 in the ballast channel as far away from

the A.C. ballast(s) as possible. The

I-232 may also be mounted on top of the fixture. The optional top mounting kit

(catalog no. TMK-80) may be ordered separately from Customer Service.

When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between

the battery pack and lamps.

2. WIRING

Refer to the wiring diagrams on the back page for the appropriate wiring of lamps and ballast. Install in accordance

with the National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.

3. INSTALLING THE CHARGE INDICATOR

Recessed Troffer Fixture – Select a convenient location with proper clearance in the ballast cover and drill or

punch a

7

/

8

″ hole (½″ knockout). Insert the

7

/

8

″ bushing into the hole. Push the plastic tube through the bushing.

Disconnect the leads from the

LED housing and route the leads down the plastic tube. Reconnect the leads to the

housing, observing the proper polarity (Red/Black or Red lead w/connector to positive (+) red tab). Push the entire
assembly back into the tube until the lens collar rests against the plastic tube. The plastic tube should be adjusted
so that the

Charge Indicator is within ¼

″ of the fixture lens. The Charge Indicator must be visible after installa-

tion. Refer to Illustration 1.

Strip Fixture – Select a convenient location on the side of the fixture so the

Charge Indicator can be seen after

installation. Allow for proper clearance inside the fixture and drill or punch a

1

/

2

″ hole. Disconnect the leads from

the

LED housing. Push the LED housing into the ½

″ hole until it is firmly locked in place. Reconnect the leads,

observing the proper polarity (Red/Black or Red lead w/connector positive (+) red tab). Refer to Illustration 2.

Illustration 1 Recessed Troffer Fixture

FIXTURE

CHARGE

INDICATOR

LIGHT

(POS LEAD)
RED/BLK OR
RED W/CONNECTOR

WHITE/RED

LEAD

+ RED

Illustration 2 Strip Fixture

I-232

OBSERVE PROPER POLARITY

I-232

4. INSTALLING THE TEST SWITCH

The

Test Switch should be mounted on the ballast channel cover of a recessed troffer, or on the side of a strip

fixture, preferably adjacent to the

Charge Indicator. Drill or punch a

1

/

2

″ mounting hole.

Note: For proper operation, use only the accessory components provided with the unit. See Page 1 of the Instruc-

tion Manual.