beautypg.com

IOTA ISL-54 User Manual

Isl-54, Important safeguards, Instruction manual

background image

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed, including the following:

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

1.

CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C. power
is supplied to the unit.

2.

CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by disconnect-
ing the unit connector.

3.

CAUTION – This is a sealed unit. The integral, high temperature Ni-Cad battery is not replaceable. Replace the
entire unit when necessary and recycle or dispose of the nickel-cadmium battery properly.

4.

DO NOT USE OUTDOORS. The ISL-54 is for use with grounded, UL Listed, damp location rated, indoor fixtures.
Not for use in heated air outlets or hazardous locations.

5. The

ISL-54 requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused A.C.

lead.

6. Do not mount near gas or electric heaters.

7. The

ISL-54 should be mounted in locations and at heights where it will not readily be subjected to tampering by

unauthorized personnel.

8. The

ISL-54 will cold strike and operate for 90 minutes one 2

′ to 4′ T5, 17W to 30W T6, or 17W to 40W T8 linear

lamp, including HO and 4 pin long compact fluorescent lamps, from 36 through 55 watts.

9. The

ISL-54 is compatible with all A.C. magnetic and electronic ballasts including multiple lamp ballasts with one

lamp operating in the emergency mode.

10. Suitable for use in damp locations.
11. For use in 0° C minimum, 50° C maximum ambient temperatures.
12. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.

13. Do not use this equipment for other than intended use.

14. Install in accordance with the National Electrical Code and local regulations.

15. Installation and servicing should be performed by qualified personnel.

16. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before

final installation.

SAVE THESE INSTRUCTIONS

ISL-54

SERIES D

EMERGENCY

LIGHTING EQUIPMENT

INSTRUCTION MANUAL

P.O. BOX 11846 TUCSON, AZ 85734

(520) 294-3292 • FAX (520) 741-2837

www.iotaengineering.com