IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1.
CAUTION – Connect the battery to the unit before applying A.C. power.
2.
CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
power is supplied to the unit.
3.
CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by discon-
necting the unit connector. In addition, the circuit board should be mounted so that no live parts are accessible
during routine maintenance or relamping.
4.
CAUTION – This is a sealed unit. The integral, high temperature Ni-Cad battery is not replaceable. Replace
the entire unit when necessary and recycle or dispose of the nickel-cadmium battery properly.
5. The
I-42-L is for use with grounded, UL Listed, indoor fixtures. The acceptability of the combination must be
determined by Underwriters Laboratories. Refer to the Engineering Considerations section for proper installation.
6. T
he
I-42-L and A.C. ballast must be on the same branch circuit.
7. The
I-42-L requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused A.C.
lead.
8. Do not mount near gas or electric heaters.
9. The
I-42-L should be mounted in locations and at heights where it will not readily be subjected to tampering by
unauthorized personnel.
10. The
I-42-L will cold strike and operate one 10W through 42W, or two 10W through 18W, 4-pin Rapid Start
compact fluorescent lamps. Contact Customer Service for additional lamp usage.
11. The
I-42-L is for use with unusually shaped fluorescent fixtures such as wall packs, sconces, and recessed
stair fixtures.
12. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition, void
warranty, and result in non-compliance with UL specifications.
13. Do not use this equipment for other than intended use.
14. Install in accordance with the National Electrical Code and local regulations.
15. Installation and servicing should be performed by qualified personnel.
16. Lighting fixture manufacturers, electricians and end users need to ensure product system compatibility before
final installation.
SAVE THESE INSTRUCTIONS
I-42-L
INSTRUCTION MANUAL
TBTS SERIES AC
10W–42W RAPID START
4 PIN COMPACT LAMP
EMERgENCy LIghTINg EqUIPMENT
P.O. BOX 11846 TUCSON, AZ 85734
(520) 294-3292 • FAX (520) 741-2837
www.iotaengineering.com