IOTA I-320 User Manual
I-320, Important safeguards, Instruction manual
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1.
CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C. power
is supplied to the unit.
2.
CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by disconnect-
ing the unit connector.
3.
CAUTION – This is a sealed unit. The integral, high temperature Ni-Cad battery is not replaceable. Replace the
entire unit when necessary and recycle or dispose of the nickel-cadmium battery properly.
4.
DO NOT USE OUTDOORS. The I-320 is for use with grounded, UL Listed, damp location rated, indoor fixtures.
Not for use in heated air outlets or hazardous locations.
5. The
I-320 requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused A.C. lead.
6. When the
I-320 is installed on the same branch circuit, refer to Illustration 3, Figures A and B for input wiring. When
installed on separate branch circuits, refer to Illustration 3, Figures C and D for input wiring. Per NEC, the
I-320 and
A.C. ballast must be on the same panel board.
7. Do not mount near gas or electric heaters.
8. The
I-320 should be mounted in locations and at heights where it will not readily be subjected to tampering by
unauthorized personnel.
9. The
I-320 will cold strike and operate one 14W through 54W T5 or 2´-4´ T8 instant start or rapid start fluorescent
lamp, including energy saving and 4-pin compact lamps for 90 minutes.
10.
The
I-320 is compatible with most A.C. ballasts (including multiple lamp) as follows:
Magnetic ballasts – one lamp emergency operation.
Electronic ballasts – one lamp emergency operation.
11. Suitable for use in damp locations.
12. For use in 0° C minimum, 50° C maximum ambient temperatures.
13. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
14. Do not use this equipment for other than intended use.
15. Install in accordance with the National Electrical Code and local regulations.
16. Installation and servicing should be performed by qualified personnel.
17. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility
before final installation.
SAVE THESE INSTRUCTIONS
I-320
TBTS SERIES AC
EMERGENCY
LIGHTING EQUIPMENT
INSTRUCTION MANUAL
P.O. BOX 11846 TUCSON, AZ 85734
(520) 294-3292 • FAX (520) 741-2837
www.iotaengineering.com