IOTA I-162 User Manual
I-162, Important safeguards, Instruction manual
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1.
CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C. power
is supplied to the unit.
2.
CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by disconnect-
ing the unit connector.
3.
CAUTION – The integral, high temperature Ni-Cad battery is replaceable. To replace the battery, disconnect the
unit connector and remove both switched and unswitched A.C. power to the fixture. Remove the lid screw and
open the lid to expose the battery. Unplug the battery connector and replace with part number 44203-412 (14.4V
Ni-Cad battery only). Recycle or dispose of the used nickel-cadmium battery properly
4.
DO NOT USE OUTDOORS. The I-162 is for use with grounded, UL Listed, damp location rated, indoor fixtures.
Do not use in heated air outlets or hazardous locations.
5. The
I-162 requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused A.C. lead.
6. When the
I-I62 is installed on the same branch circuit, refer to Illustration 2, Figures A and B for input wiring. When
installed on separate branch circuits, refer to Illustration 2, Figures C and D for input wiring. Per NEC, the
I-I62 and
A.C. ballast must be on the same panel board.
7. Do not mount near gas or electric heaters.
8. The
I-162 should be mounted in locations and at heights where it will not readily be subjected to tampering by
unauthorized personnel.
9. The
I-162 mounts on top of the fixture or adjacent to the fixture on an optional T-bar mounting bracket.
10.
The
I-162 will cold strike and operate two 4
′ instant start, rapid start, U shape or circline fluorescent lamps, T8
through T12 fluorescent lamps, two 24W-50W long compact lamps, or two 54W T5 fluorescent lamps.
11.
The
I-162 operates lamps as follows:
Two 4
′ T8-T12 lamps, two 24W-50W long compact, or two 54W T5 lamps for 90 minutes.
12. Suitable for use in damp locations.
13. For use in 0° C minimum, 50° C maximum ambient temperatures.
14.
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition, void
warranty, and result in non-compliance with UL specifications.
15. Do not use this equipment for other than intended use.
16. Install in accordance with the National Electrical Code and local regulations.
17. Installation and servicing should be performed by qualified personnel.
18. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before
final installation.
SAVE THESE INSTRUCTIONS
I-162
SERIES AC
PARALLEL OPERATION
EmERgENCy
LIghTINg EqUIPmENT
INSTRUCTION MANUAL