IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1.
CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
power is supplied to the unit.
2.
CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by discon-
necting the unit connector.
3.
CAUTION – This is a sealed unit. Components are not replaceable. Replace the entire unit when necessary.
4.
CAUTION – Installation and servicing should be performed by qualified personnel only. De-energize before
opening.
5.
DO NOT USE OUTDOORS. The ILB-SL-CP is for use with grounded, UL Listed, damp location rated and
enclosed and gasketed, indoor fixtures. Not for use in heated air outlets or hazardous locations.
6. The
ILB-SL-CP requires an unswitched A.C. power source of 120 to 277 volts AC, 50/60Hz.
7.
The
ILB-SL-CP
and A.C. driver
must be on the same branch circuit.
8. Do not mount near gas or electric heaters.
9. The
ILB-SL-CP should be mounted in locations and at heights where it will not readily be subjected to tamper-
ing by unauthorized personnel.
10. The
ILB-SL-CP will supply 10-60VDC output at the individual rated specification for 90 minutes. See individual
units for output specifications.
11. Suitable for use in damp locations and in enclosed and gasketed fixtures.
12. For use in 0° C minimum, 55° maximum ambient temperatures.
13. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition, void
warranty, and result in non-compliance with UL specifications.
14. Do not use this equipment for other than intended use.
15. Install in accordance with the National Electrical Code and local regulations.
16. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before
final installation.
SAVE THESE INSTRUCTIONS
ILB-SL-CP
TBTS
EMERGENCY
LIGHTING EQUIPMENT
FOR LED
INSTRUCTION MANUAL
P.O. BOX 11846 TUCSON, AZ 85734
(520) 294-3292 • FAX (520) 741-2837
www.iotaengineering.com
CLASS 2 OUTPUT