IOTA ISL-540-35W User Manual
Isl-540, Important safeguards, Instruction manual
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1.
CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
power is supplied to the unit.
2.
CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by discon-
necting the unit connector.
3.
CAUTION – This is a sealed unit. The integral, high temperature Ni-Cad battery is not replaceable. Replace
the entire unit when necessary and recycle or dispose of the nickel-cadmium battery properly.
4.
DO NOT USE OUTDOORS. The ISL-540 is for use with grounded, UL Listed, damp location rated, indoor
fixtures. Not for use in heated air outlets or hazardous locations.
5. The
ISL-540 requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused
A.C. lead.
6. Do not mount near gas or electric heaters.
7. The
ISL-540 and A.C. ballast must be on the same branch circuit.
8. The
ISL-540 should be mounted in locations and at heights where it will not readily be subjected to tampering
by unauthorized personnel.
9. The
ISL-540 will cold strike and operate for 90 minutes one 2
′ to 4′ T5, one 27W-46W T6, or one 17W-40W T8
linear lamp, including HO and 4-pin long compact fluorescent lamps, from 36 through 55 watts.
10. The
ISL-540 is compatible with all A.C. magnetic and electronic ballasts including multiple lamp ballasts with
one lamp operating in the emergency mode.
11. Suitable for use in damp locations.
12. For use in 0° C minimum, 50° C maximum ambient temperatures.
13. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
14. Do not use this equipment for other than intended use.
15. Install in accordance with the National Electrical Code and local regulations.
16. Installation and servicing should be performed by qualified personnel.
17. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before
final installation.
SAVE THESE INSTRUCTIONS
ISL-540
TBTS SERIES D
EMERGENCY
LIGHTING EQUIPMENT
INSTRUCTION MANUAL
P.O. BOX 11846 TUCSON, AZ 85734
(520) 294-3292 • FAX (520) 741-2837
www.iotaengineering.com