3 flue and ventilation, Back boiler unit – Glow-worm 56/3 Back Boiler User Manual
Page 7

7
221724B
3 Flue and Ventilation
Diagram 3.1
3.1 General
The general recommendations of the current issue of
BS5440 Part 1 should be followed.
In all cases the flue should be lined, preferably with a flexible
liner.
It is essential that the flue has an equivalent height of at least
2.5m (8.2ft) measured from the flue connection on the
appliance. The first 600mm, at least, above the draught
diverter must be vertical.
The flue socket is designed to take flue pipe to BS567. If
flue pipe conforming to a different standard is used a suitable
adapter must be fitted and secured to the flue socket.
A flexible flue liner may be used, with connection to the back
boiler flue socket made with a short vertical piece of flexible
liner, see diagram 3.2.
The existing flue may not be completely sound.To prevent
any possibility of leakage, additional sealing MUST be
carried out between the base of the chimney and the flue
liner.
The end of the liner at the chimney top must be adequately
sealed and clamped, using proprietary fittings suitable for the
flue liner used, see diagram 3.1.
The flue should, preferably, end above ridge height but at
least above the eaves of a pitched roof. Use a certificated
terminal.
If the flue is to pass through or near any combustible material
it should be installed in accordance with the current issue of
BS5440 Part 1. If in doubt seek advice from the local gas
undertaking or Hepworth Heating Ltd.
3.2 Existing Chimney
An existing brick chimney must be thoroughly swept and all
debris cleared away before lining.
Remove any register plates, dampers and the like.
Alternatively it may be locked in the open position.
A flexible flue liner is preferred but a rigid liner may be used,
with connection to the back boiler flue socket made with a
short vertical piece of flexible liner, see diagram 3.2.
Any air supply that enters the builder’s opening other than by
the front opening, that is underdraught openings and the like
must be completely sealed off.
The sealing plate also prevents debris falling and gives the
flue better insulation, reducing the possibility of
condensation, see diagram 3.1.
Check the flue system efficiency before installing the back
boiler.
3.3 New Chimney
A newly built chimney can be lined with a moisture resistant
lining, such as salt glazed pipe, of an appropriate diameter
as specified in the Building Regulations
In the case of a salt glazed lined flue, it is recommended that
a short vertical length of flue pipe, preferable flexible metallic
be used, fixed and sealed to the back boiler flue socket,
made good with approved packing and parged with fire
cement, see diagram 3.2.
BACK
BOILER
UNIT
6197
SEALING AND
CLAMPING
PLATE
AIR
SPACE
150mm (6in) plug of Mineral Wool or similar
600mm
Diagram 3.2
7194
APPROVED
SEAL
FLEXIBLE
LINER
BACK BOILER
RIGID
FLUE
LINER
Existing Flue Fitted with
Approved Lining
SEALING
PLATE