Installation, Dc b e a – Glow-worm Clearly Heat Pumps - Standalone Module System User Manual

Page 18

background image

0020096321_00 - 07/10 - Glow-worm

- 16 -

INSTALLATION

6.3 Hydraulic

module

• Connect the hydraulic module to an electrical panel via an

independent protective system (32A differential breaker with
a separation of at least 3mm between all contacts).

Additional protection may be required during installation to
ensure overvoltage category II.

EBUS Connection

1

Key
1

Ebus connection terminal

• Connect a 2 x 0.75 mm ² cable to the hydraulic module’s

BUS terminal (2).

• Connect the Ebus cable to the Systempro control unit.

230V Connection

• Connect a 3 x 4 mm ² cable to the hydraulic module’s power

terminal 230V (1).

• Connect

the

hydraulic module’s power cable to the

installation’s electrical panel: single-phase network 230V +
neutral + earth.

6.4

Systempro control unit

• The electrical installation in the dwelling must permit the

power supply to the equipment to be isolated by a double
pole isolation switch and be fused. The double pole isolation
switch must incorporate a gap of 3mm between the contacts.

• Use a power cable suitable for the mains connection,

minimum 0.75 mm. If the cable is damaged, it must be
replaced by a qualifi ed engineer.

6.4.1

Wiring to the Systempro control unit

D

C

B

E

A

5

1

2

3

4

Key
1

230 V power cable

2

Break out tab

3 Anti-tamper

connection

4 Power

connection

5 Control

unit

• Gently remove the break out tab (2) from the control unit with

pliers (A).

• Connect the control unit following the order (B) to (D).

• Pass the power cable (1) through the anti-tamper connector

(3).

• Connect the power supply to the 230 V connector (4)

following the instructions given on the connector.

• Tighten the power cable (1) in the anti-tamper connector (3).