E-Tech EH series User Manual
Page 7

13
12
2.2 Temperature of pumped fl uids
The pumped liquids must remain within certain 
temperature limits: 
• with EPDM seals: -15° to +110°C 
• with VITON seals: -15° to +90°C 
• with NBR seals: -15° to +80°C 
3. INSTALLATION AND PREPARATION 
3.1 Conditions of use 
The horizontal electric pumps are multistage pumps 
operating with clockwise rotation looking at the electric 
pump from the motor fan. 
• Pump not self-priming.
• Maximum density of the pumped liquid: 1.1 kg / dm³.
• Allowed voltage variation: ± 5% (single-phase voltage 
220÷240V 50Hz, three-phase 380÷415V / 220÷240V 
50Hz).
• Degree of protection: IP55.
• Sound pressure level lower than 70 dB (A).
• Dimensions and overall dimensions (See technical 
catalog).
• Maximum ambient temperature: +40°C.
3.2 Minimum suction pressure 
Check the characteristic curves of electric pumps to 
evaluate the NPSH factor and avoid cavitation problems 
(case in fi gure 1.B on page 4). 
3.3 Maximum suction pressure
It is important to maintain the sum of input and output 
pressure; this latter, with closed opening, shall always 
be lower than the allowed maximum operating pressure 
for the electric pump. However, the maximum operating 
pressure shall never exceed 10bar (case in Figure 1.A 
on page 4). 
3.4 Minimum
nominal
fl ow rate
The operation of the electric pump at a lower level 
of nominal minimum allowed fl ow rate may result in 
excessive overheating, which may damage the electric 
pump. 
m
The electric pump must never be operated with 
the discharge valve closed.
4. ELECTRICAL CONNECTIONS
c
Before beginning to work on the electrical pump, 
make sure that you have disconnected the 
electricity from the power supply mains and that 
it cannot be accidentally reconnected.
The installation of the electrical pump can involve a 
certain amount of complexity. For this reason, it must be 
performed by competent and authorized installers.
Legend fi gure 1 (see also p. 4):
1. Filter (maximum passage section of 1 mm)
2. Valve-fi lter (maximum passage section of 1 mm)
3. Gate valve
4. Manometer
5. Check Valve
6. Positive slope
7. Pipe anchoring elements
8. Storage container
There may be two important application cases: 
• Case outlined in fi gure 1.A (see p. 4). System with pump 
under head (positive head), be it a tank as shown in the 
fi gure or the civil water supply network, the system must 
provide protection in case of lack of water.
• Case outlined in fi gure 1.B (see p. 4): Plant with suction
pump.
4.1 Mounting 
Install the pump in an accessible place, protected against 
frost and as close as possible to the water collection 
point.
The electric pump must be fi rmly attached to the base by 
means of bolts. 
Allow enough space around the electric pump to allow 
use and maintenance operations, as well as any possible 
collection of hazardous liquids or liquids that need to be 
drained at a temperature above 60 °C. In any case, make 
sure that there is a clearance of at least 100 mm from the 
cooling fan. 
To avoid unnecessary stress to the pump body install 
support brackets (see Figure 1, note 7 on page 4) to 
support the inlet and outlet pipe. 
To avoid air pockets harmful to the electric pump 
operation, provide for an inclination of the inlet pipes of at 
least 2% (see Figure 1, note 6 on page 4.) 
Protect the pump from any water hammer through a check 
valve placed in the delivery pipe. Install a shutoff valve 
upstream and downstream of the pump so as to allow its 
isolation in case of maintenance and disassembly. 
The diameter of inlet pipes should never be less than the 
diameter of the inlet opening. 
For the diameter of the connection piping refer to the 
following table:
Pump type
DN threaded sleeves
Suction
Delivery
3
1" ¼
1"
5
1" ¼
1"
9
1" ½
1" ¼
4.2 Electrical
connections
c
Before beginning to work on the electrical pump, 
make sure that you have disconnected the 
electricity from the power supply mains and that 
it cannot be accidentally reconnected.
Connections must only be performed by an authorized 
electrician in compliance with law in force.
c
Verify that the data on the name plate match 
the nominal values for the power line. Make 
the connection after verifying the existence of 
a working grounding circuit. It is the installer’s 
responsibility to perform the connection in 
compliance with regulations in force in the 
country of installation.
Connect the electric pump by means of an external 
network switch having a minimum distance between the 
contacts of at least 3 mm on all poles. 
Connect the wires to the motor according to the diagram 
shown inside the terminal cover. 
• For single-phase versions see Figure 3.A on page 5.
• For three-phase versions see Figure 3.B on page 5.
c
Use cable complying with the regulations, 
equipped with ground wire (3 conductors for 
single-phase versions and 4 conductors for 
three phase versions) 
c
Avoid any way contact between the electric 
cables and the pipes or other parts of the pump; 
carefully insulate the cables from moisture. 
The single-phase versions are accompanied by internal 
capacitor to the output variable.
For all single-phase versions, the engine is protected 
against overloads by means of a thermal device (overload 
cut-out) inserted into the winding.
The three-phase versions require external protection 
(quick disconnect magnetic overload cut-out) with a 
tripping time set to:
• Less than 10 seconds with 5 times I
N
• Less than 10 minutes with 1.5 times I
N
I
N
= maximum current value indicated on the rating plate.
The pump must supplied through a residual current 
device (RCD) with a rated residual operating current 
≤30mA.
4.3 Checking the direction of rotation
After connecting the power supply, the direction of 
rotation can be inverted in the 3-phase versions; in this 
case, performance will be signifi cantly lower than the 
nominal values. To verify a correct connection, proceed 
as follows:
1) Start the pump, check that the direction of rotation is
as indicated by the arrow. Warning! If this operation is 
made under dry conditions, it shall not last more than 
a few seconds. 
2) To correct the rotation is suffi cient to invert the two
phases.
c
Do not fail to connect the grounding.
5. COMMISSIONING
CAUTION: The pump should NOT be started without 
having been fi lled fi rst. Its dry use may irreparably 
damage the mechanical seal. 
5.1 Filling 
5.1.1 Electric pump being charged (see fi gure 
1.A and fi gure 2.A on page 4 and 5)
1. Close the gate valves on the delivery side of the
electric pump so as not to let the fl uid that you are 
using for fi lling the electric pump circulate in the 
circuit. 
2. Remove the fi lling cap (see Figure 2.A on page 5). 
3. Open the gate valve placed on the suction side of the 
pump to drain the fl uid present in the pump. Make 
sure that the difference in level between the pump 
and the head is such as to ensure a complete fi lling of 
the pump. 
4. When there is a homogenous fl ow from the fi lling
hole, place the fi lling cap carefully back to its position.
5. Start the pump and check, only on three-phase
versions, that the direction of rotation is as indicated 
by the arrow. To correct the direction of rotation is 
suffi cient to invert the two phases. 
6. Slowly open the valve gate on the delivery side till its
stroke end.
m
Pay particular attention to point 3 - when the 
pump is fi lled with hot liquids or hazardous 
liquids, fl uid leaking from the drain cap could hit 
more people; make sure to be in a safe position 
during this operation. In this case, close the 
gate valve after the release of a constant fl ow 
of liquid from the cap before closing it in order to 
avoid contact with the liquid. 
m
Depending on the temperature of the pumped 
liquid, the electric pump surfaces can reach high 
temperatures. If deemed necessary, provide for 
guards to prevent accidental contact. 
5.1.2
Pump during suction operations (see
fi gure 1.B 2.A fi gures and on page 4 and
5)
1. Close the gate valves on the delivery side of the
electric pump so as not to let the fl uid that you are 
using for fi lling the electric pump circulate in the circuit 
and open the gate valve on the suction side. 
2. Remove the fi lling cap (see Figure 2.A on page 5). 
3. Fill the pump as outlined in fi gure 2.A until the fl uid 
comes out from the fi lling hole.
4. Close the fi lling cap carefully. 
5. Start the electric pump and check, only in three-phase 
versions, that the direction of rotation is as indicated 
by the arrow. To correct the direction of rotation is 
suffi cient to invert the two phases. 
7. Slowly open the gate valve on the delivery side till its
stoke end.
m
Depending on the temperature of the pumped 
liquid, the electric pump surfaces can reach high 
temperatures. If deemed necessary, provide for 
guards to prevent accidental contact.
