beautypg.com

Voltage transducer, 3-wire – Delta RMC70 User Manual

Page 38

background image

RMC70 Startup Guide

36

Delta Computer Systems, Inc.

12-pin Axis
Connector

+Analog Out

-Analog Out

Pwr Common

+Pwr

Power Supply

+Pwr

Cmn

+Analog In

Jumper for 4-20 mA

-Analog In

Cmn

+10Vdc Exciter

Case

Signal Common

12-pin Axis
Connector

+Analog Out

Common

Power Supply

+24 VDC

Cmn

+Analog In

Jumper for 4-20 mA

-Analog In

Cmn

+10Vdc Exciter

Case

+Pwr

AA Module Voltage Transducer Wiring

Voltage Transducer, 4- or 5-Wire

Voltage Transducer, 3-Wire

To reduce electrical interference:

-Analog In and Cmn must be
connected, either internal to the
transducer or externally as close
as possible to the transducer.

Use individually shielded
twisted-pair wire.

Connect cable shield to earth
ground on one end only.

If transducer has only one
common, connect Pwr Supply
Common and RMC Cmn to it. For
best results, make this
connection at the transducer.