Voltage transducer, 3-wire – Delta RMC70 User Manual
Page 38
RMC70 Startup Guide
36
Delta Computer Systems, Inc.
12-pin Axis
Connector
+Analog Out
-Analog Out
Pwr Common
+Pwr
Power Supply
+Pwr
Cmn
+Analog In
Jumper for 4-20 mA
-Analog In
Cmn
+10Vdc Exciter
Case
Signal Common
12-pin Axis
Connector
+Analog Out
Common
Power Supply
+24 VDC
Cmn
+Analog In
Jumper for 4-20 mA
-Analog In
Cmn
+10Vdc Exciter
Case
+Pwr
AA Module Voltage Transducer Wiring
Voltage Transducer, 4- or 5-Wire
Voltage Transducer, 3-Wire
To reduce electrical interference:
-Analog In and Cmn must be
connected, either internal to the
transducer or externally as close
as possible to the transducer.
Use individually shielded
twisted-pair wire.
Connect cable shield to earth
ground on one end only.
If transducer has only one
common, connect Pwr Supply
Common and RMC Cmn to it. For
best results, make this
connection at the transducer.