beautypg.com

Air for combustion and ventilation – Desa GA3700 User Manual

Page 7

background image

www.desatech.com

113109-01G

7

1. Determine the volume of the space (length

x width x height).

Length x Width x Height =__________cu. ft.
(volume of space)

Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)

If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.

2. Multiply the space volume by 20 to determine

the maximum Btu/Hr the space can support.

________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) x 20
= 51,200 (maximum Btu/Hr the space can
support)

3. Add the Btu/Hr of all fuel burning appliances

in the space.

Vent-free fireplace

__________ Btu/Hr

Gas water heater*

__________ Btu/Hr

Gas furnace

__________ Btu/Hr

Vented gas heater

__________ Btu/Hr

Gas fireplace logs

__________ Btu/Hr

Other gas appliances* + _________ Btu/Hr

Total

= _________ Btu/Hr

* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.

Example:

Gas water heater

__________ Btu/Hr

Vent-free fireplace

+ _________ Btu/Hr

Total

= _________ Btu/Hr

4. Compare the maximum Btu/Hr the space

can support with the actual amount of Btu/
Hr used.

_______ Btu/Hr (maximum the space can
support)

_______ Btu/Hr (actual amount of Btu/Hr
used)

Example: 51,200 Btu/Hr (maximum the

space can support)

73,000 Btu/Hr (actual amount of
Btu/Hr used)

The space in the above example is a confined
space because the actual Btu/Hr used is more
than the maximum Btu/Hr the space can sup-
port. You must provide additional fresh air. Your
options are as follows:
A. Rework worksheet, adding the space of an

adjoining room. If the extra space provides an
unconfined space, remove door to adjoining
room or add ventilation grills between rooms.
See Ventilation Air From Inside Building.

40,000
33,000
73,000

AIR FOR COMbUSTION AND VENTILATION

Continued

Figure 3 - Ventilation Air from Inside

Building

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills

Into Adjoining Room,

Option 2

Ventilation

Grills

Into Adjoining

Room,

Option 1

12"

12"

B. Vent room directly to the outdoors. See

Ventilation Air From Outdoors, page 8.

C. Install a lower Btu/Hr fireplace, if lower Btu/Hr

size makes room unconfined.

If the actual Btu/Hr used is less than the maximum
Btu/Hr the space can support, the space is an
unconfined space. You will need no additional
fresh air ventilation.

WARNING: If the area in

which the heater may be oper-

ated does not meet the required

volume for indoor combustion

air, combustion and ventilation

air shall be provided by one of

the methods described in the

National Fuel Gas Code, ANSI

Z223.1/NFPA 54, the Internation-

al Fuel Gas Code, or applicable

local codes.

vENTILATION AIR

Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconfined space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the floor on the
wall connecting the two spaces (see options
1 and 2, Figure 3). You can also remove door
into adjoining room (see option 3, Figure 3).
Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and
Ventilation
for required size of ventilation
grills or ducts.

This manual is related to the following products: