INSTALLATION

Continued

CAUTION: Make sure exter-

nal regulator has been installed

between propane/LP supply and

fireplace. See guidelines under

Connecting Fireplace to Gas

Supply, page 15.

pRESSURE TESTING GAS SUppLY
pIpING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect fireplace with its appliance

main gas valve (control valve) and equip-
ment shutoff valve from gas supply piping
system. Pressures in excess of 1/2 psig
will damage fireplace regulator.

2. Cap off open end of gas pipe where equip-

ment shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.

4. Check all joints of gas supply piping sys-

tem. Apply noncorrosive leak detection fluid
to all joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Reconnect fireplace and equipment

shutoff valve to gas supply. Check recon-
nected fittings for leaks.

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig-

ure 21).

2. Pressurize supply piping system by either

opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.

3. Check all joints from gas meter to equip-

ment shutoff valve for natural gas or
propane/LP supply to equipment shutoff
valve for propane/LP (see Figures 22 or
23). Apply noncorrosive leak detection
fluid to all joints. Bubbles forming show a
leak.

4. Correct all leaks at once.

Figure 21 - Equipment Shutoff Valve

Open

Closed

Equipment
Shutoff
Valve

Figure 23 - Checking Gas Joints for

Propane/LP Gas

Equipment
Shutoff Valve

Gas Control Valve

Gas Meter

Figure 22 - Checking Gas Joints for

Natural Gas

Equipment Shutoff Valve

Propane/LP
Supply Tank

Gas Control Valve

pRESSURE TESTING FIREpLACE GAS
CONNECTIONS
1. Open equipment shutoff valve (see Fig-

ure 21).

2. Open main gas valve located on or near

gas meter for natural gas or open pro-
pane/LP supply tank valve.

3. Make sure control knob of fireplace is in

the OFF position.

4. Check all joints from equipment shutoff

valve to gas control valve (see Figures
22 or 23). Apply noncorrosive leak de-
tection fluid to all joints. Bubbles forming
show a leak.