35

Magnum 7500 Wiring Diagram


IMPORTANT: Incorrectly installed fan limit controls can cause electrical shock, shorting out of the
circuit and damage to the unit. The Brass jumper wire must be removed on the fan limit control.
Refer to the installation, setting and operation instructions provided with the fan limit control.

The fan limit control heat settings are as follows: Fan on 140 deg., Fan off 90 deg., High Limit 200 deg.
If the fan on is set too high the high limit might trip out the auger motor and the fire will go out. If the fan
on is too low the fan will cycle on and off too much. If the fan off is set too low the blower will distribute
cold air and the furnace will not operate efficiently.



Circuit
Board
Control

AES #
MF3593

2 wire low voltage thermostat

Power Cord
Receptacle

Power cord
Black

Green
Ground

Fuel Stirrer
Gear motor

AES# MF3540

Exhaust Motor

AES # MF3542

Auger Gear
Motor

AES # CF26

Blower
1240 cfm

AES # CF24
Grainger Motor#3M393

white

white

Power cord white

Black to fan limit control
Fan side

Fan

Black to
fan limit

Gray

Green

High Limit

power power

Remove
clip

Blue

Auger
Safety
Sensor

White neutral

White neutral

Brown

Red

Black

Green

Orange

Note: Purple wire is capped and not used

Honeywell # L4064B 2228
Grainger # 2E818 5” insertion
AES # CF23

AES # MF3537

200 deg. High
limit snap disk

A 200-degree high limit
control has to be installed
in the primary furnace
duct work below the
Magnum 7500 hot air
outlet in a supplementary
furnace installation only.