1 post installation tests, 2 before initial startup, 3 initial start – Generac Power Systems 004270-1 User Manual
Page 37: 4 testing under load, Post installation tests, Before initial startup, Initial start, Testing under load
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Section 3 - Post-installation Start-up Checks
QUIETPACT™ 75D Recreational Vehicle Generator
POST- (
INSTALLATION
START-UP
CHECKS
3.1 POST INSTALLATION TESTS
The generator set was factory-tested and adjusted.
You should not be required to adjust the unit any fur
ther, except under special circumstances.
-A WARNING A-
A
Do not make any unnecessary adjustments.
Factory settings are correct for most applica
tions, When making adjustments, however, be
careful to avoid overspeeding the engine.
3.2 BEFORE INITIAL STARTUP
Before starting, complete the following:
1.
Check the engine crankcase oil level and, if nec
essary, fill to the dipstick “FULE’ mark (cross-
hatched area) with the recommended oil. Do not
fill above the FULL mark.
2.
Check the fuel supply. Fuel lines must have been
properly
purged
and
leak-tested
in
accordance
with applicable fuel codes. All fuel shutoff valves
in the fuel supply lines must be open.
3.3 INITIAL START
When you are absolutely certain that the unit has
been properly installed and prepared for use, start
the engine as follows:
1.
Turn off all electrical loads. Do this by setting the
generator’s line breakers to their “OFF” (or open)
position.
2.
Refer to Part I, Section 2.4, “Starting the
Generator” (Page 8), for cranking and starting
instructions.
The
engine
may
require
more
cranking for initial starting, since the fuel lines
have to be primed (use of the preheat switch will
operate the generator’s electrical fuel pump and
shorten this time).
3.
Let the engine warm up for about five minutes to
allow internal temperatures to stabilize.
4.
Carefully inspect the engine/generator for fuel, oil,
and exhaust system leaks. Before proceeding to the
next step, correct any leakage immediately.
5.
When all tests and adjustments at no-load are
completed,
apply
electrical
loads
and
check
for
proper
operation
under
load.
See
Section
3.4. Run the unit at least 30 minutes, with
loads applied.
6
.
Turn off all electrical loads by setting the gen
erator’s line breakers to their “OFF” (or open)
position.
7.
Let the unit run at no-load for a few minutes to
stabilize
internal
engine/generator
temperatures.
Then, shut down the engine.
NOTE:
The
generator
set
was
thoroughly
tested
and
adjusted at the factory before shipping. No addi
tional
adjustment
should
be
necessary.
Only
trained,
qualified
service
technicians
should
perform adjustments outlined in this manual.
3.4 TESTING UNDER LOAD
Apply electrical loads equal to about 50 to 75 percent
of the unit's rated wattage/amperage capacity.
Let the unit run at least 30 minutes with load applied.
During this part of the test, check that the unit is not
running excessively hot and that adequate cooling air
flow is available. You must not allow the unit to over
heat during prolonged operation.
NOTE:
The generator engine is equipped with a high
coolant temperature switch. The switch has normal
ly open (N.O.) contacts. When the engine coolant
temperature is too high, switch contacts close, and
the engine shuts down automatically.
GENERAC RECOMMENDS THAT YOU TEST THE
GENERATOR FOR ADEQUATE COOLING.
Generac* Power Systems, Inc.
35