Status, Indicates, Check/repair – Sears 9MPD125L20B1 User Manual
Page 45: Concentric termination, Vent termination clearances, Concentric vent termination naha001cv & naha002cv, Concentric vent termination, Warning
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

HONEYWELL SV9541M "SMART VALVE" Trouble shooting continued
LED
STATUS
INDICATES
CHECK/REPAIR
6 Flashes +
3 Flashes
Soft Lockout.
Last failure was pressure switch
Maximum recycle count exceeded
Combustion air blower is de-energized, Circulating blower is de
energized after the "OFF" delay.
After 5-minute delay time, control system will reset and initiate a
new ignition seguence,
Ignition system control switch must be in the ON position.
Pressure switches operation, tubing, and wiring.
Restrictions in furnace air intake or vent piping.
Fligh winds blowing against vent.
6 Flashes +
4 Flashes
Soft Lockout.
Last failure was limit circuit opened during run.
Combustion air blower is de-energized. Circulating blower is
de-energized alter the "OFF" delay.
After 5-minute delay time, control system will reset and initiate a
new ignition sequence,
Main limit switch.
Limit and rollout switch wiring is in good condition and securely
connected.
Restriction in duct work.
Dirty filter
7 Flashes
Soft Lockout.
Blower failure (typical)
Limit trip took longer than 2 minutes to reset.
System will start a new ignition sequence after 1 hour, if call for
heat still present.
Dead blower.
Blocked duct work.
11. Concentric Termination
Vent Termination Clearances
WARNING
CARBON MONOXIDE POISONING, FIRE AND
EXPLOSION HAZARD
Failure to properly vent this furnace could result in
death, persona! injury and/or property damage.
Inlet and outlet pipes may NOT be vented directly
above each other (standard vent terminals).
1.
Determine termination locations based on clearances spe
cified in following steps and as shown in Figure 7,
Figure 45 through Figure 50.
2.
The vent termination must be located at least 12 ' above
ground or normally expected snow accumulation levels.
3.
Do NOT terminate over public walkways. Avoid areas
where condensate may cause problems such as above
planters, patios, or adjacent to windows where steam may
cause fogging.
4.
The vent termination shall be located at least 4' horizontally
from any electric meter, gas meter, gas regulator, and any
relief equipment. These distances apply ONLY to U.S.
installations.
5.
The vent termination is to be located at least 3' above any
forced air inlet located within
10
’ ; and at least
10
’ from a
combustion air intake of another appliance, except another
direct vent furnace intake.
6
.
In Canada, the
Canadian Fuel Gas Codelakes precedence
over the preceding termination instructions.
Concentric Vent Termination
NAHA001CV & NAHA002CV
Kit#
These kits are for vertical or horizontal termination of the combus
tion air inlet and the exhaust vent pipes on Category IV gas-fired
condensing furnaces. The NAFIA001CV kit can be used for 3 ” di
ameter pipe systems. The NAHA002CV kit can be used for 2 ” di
ameter pipe system. Refer to Table 13 for the correct pipe size for
the furnace. Both the combustion air inlet and the exhaust vent
pipes must attach to the termination kit. The termination kit must
terminate outside the structure and must be installed per the in
structions outlined below for vertical or horizontal termination. Ver-
440 01 1020 04