Honeywell sv9541m "smart valve" trouble shooting, 144 i – Sears 9MPD125L20B1 User Manual
Page 44
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

The
6
+ X designation indicates a combination of flash codes:
6
flashes shows the control is in soft lockout, followed by X flashes to indicate
the reason the control went into soft lockout. Last status code indicates repair to address first
HONEYWELL SV9541M "SMART VALVE" Trouble shooting
LED
STATUS
INDICATES
CHECK/REPAIR
Off
No power to system control.
Line voltage input at LI and Neutral connectors on ST9160B Fan Timer.
Low voltage (24V) power at 24 VAC and COM terminals on ST9160B
System wiring harness is in good condition and securely connected.
Heartbeat
Bright - Dim
Normal indication whenever the system is powered, unless some
abnormal event has occurred.
Not Applicable - Normal Operation (stand by or call for heat)
2 Flashes
Pressure switches closed when it should be open
(I.e. when call for heat begins).
(Combustion blower is not energized until pressure switches
opens)
Pressure switches stuck closed (system will wait for pressure switch to
open).
Pressure switches miswired or jumpered.
3 Flashes
Pressure switches, open when they should be closed (i.e. longer
than 30 seconds after combustion blower/inducer is energized).
System goes into 5-minute delay period, with combustion blower/
inducer off. Atendofthe 5-minute delay, another cycle will begin.
Ignition system control switch must be in the ON position.
Pressure switches operation, tubing, and wiring.
Restrictions in furnace air intake or vent piping.
4 Flashes
Main Limit or Roll Out Switch is open.
Combustion blower is energized. Circulating blower is energized
heat speed.
Main limit switch.
Manual reset burner rollout switch.
Limit and rollout switch wiring is in good condition and securely
connected.
5 Flashes
Flame signal sensed out of proper sequence.
Combustion blower is energized. Circulating blower is energized
heat speed after the "ON" delay.
Flame at pilot burner.
6 Flashes +
1 Flash
Soft Lockout.
Failed to light pilot during 90 sec. trial for ignition
Combustion air blower is de-energized. Circulating blower is de
energized after the "OFF" delay.
After 5-minute delay time, control system will reset and initiate a
new ignition sequence.
Gas supply off or pressure too low or high for appliance to operate.
Damaged or broken HSI element
Line voltage HOT lead wire not connected to LI terminal on ST91 GOB.
Furnace not properly earth grounded.
Flame sense rod contaminated or In incorrect position.
Pilot burner located In incorrect position.
Pilot burner lead wires are in good condition and popery connected.
Pressure switches operation, tubing, and wiring.
6 Flashes +
2 Flashes
Soft Lockout.
Last failure was Flame Sense lost during run.
Maximum recycle count exceeded
Combustion air blower is de-energized. Circulating blower is
de-energized alter the "OFF" delay.
After 5-minute delay time, control system will reset and initiate a
new ignition sequence.
Gas supply off or pressure too low or high for appliance to operate.
Line voltage HOT lead wire not connected to LI terminal on ST91 GOB.
Furnace not properly earth grounded.
Flame sense rod contaminated or in incorrect position.
Pilot burner located in incorrect position.
Pilot burner lead wires are in good condition and properly connected.
Cycling, pressure switch
Condensate drain blocked
Pressure switches operation, tubing, and wiring.
144 I
440 01 1020 04