Carrier 38HQ User Manual
Page 8
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

CONNECT
GROUND
LEADS
AND
POWER
WIRING
Connect ground leads to the ground lug in
control box for safety. Connect power wiring. See
Fig. 8. Splice compressor section line power leads
to yellow and black pigtails, and outdoor coil power
leads to brown and blue pigtails. Use wire nuts and
tape each connection.
CONNECT
POWER
LEADS
FROM
INDOOR
COMPRESSOR
SECTION
TO
OUTDOOR
COIL thru outdoor disconnect switch. From dis
connect switch extend leads thru hole provided in
coil basepan (Fig. 1) and into line voltage section
of junction box, Fig. 24. Splice leads to black and
blue pigtails with wire nuts.
SEE
INDOOR
FAN
COIL
AND
ELECTRIC
HEATER
INSTALLATION,
START-UP
AND
SERVICE INSTRUCTIONS for line power wiring
details. All control wiring connections are shown
in this booklet.
CONNECT CONTROL POWER WIRING (24 v)
— Extend wiring thru 7/8-in. grommeted hole in
compressor section top panel (Fig. 2), and to control
wiring terminal board on side of control box. Con
nect leads to terminal board as shown in Fig. 9.
Extend and connect control wiring from compressor
section to outdoor coil as required. Make splice
connections in low voltage section of coil junction
box.
Use indoor fan coil transformer as 24-v supply for
system. At least a 60-va transformer is recom
mended.
Carrier
approved
indoor
units
are
equipped with a 60-va transformer. See Indoor
Unit data.
Use Carrier accessory
indoor thermostat with
subbase. Table 4.
START-UP
The
38HQ
Indoor
Section
Compressor
is
equipped with a crankcase heater. It is recom
mended that heater be energized a minimum of 24
hours before starting unit. To energize heater only,
turn the thermostat to OFF position and close
electrical disconnect to heat pump.
Heat Anticipator Settings for Room Thermo
stat (HH07AT071) — Set anticipator settings for
room
thermostat
according
to
Table
6.
These
settings may be changed slightly to provide a greater
degree of comfort for a particular installation.
> Table 6 — Thermostat Anticipator Settings
INDOOR
COMPR
SECTION
OUTDOOR
COIL
FIRST-
STAGE
ANTICI
PATOR
SETTING
INDOOR
UNIT WITH
ELECTRIC
HTR
KW
SECOND-
STAGE
ANTICI
PATOR
38HQ
HEATER
SETTINGS
(Ampi
40AQ
Fan Coil
5 0
120
940
with
7 5
10.0
25
127
940
40AQ Htrs
12 0
15 0
134
940
Fixed
40FS/28HO,VQ
50
140
960
with 40FQ
Htrs
20 0
146
960
25 0
40QB Fan Coil
with 40QB Htrs.
30 0
75
Accessory Outdoor Thermostat provides adjust
able outdoor control of accessory electric heater
(used on indoor fan coil). This thermostat makes
contact when a drop in outdoor temperature occurs.
It energizes a stage of electric heat when the outdoor
temperature setting is reached, provided the room
thermostat is on the second stage of heating. One
outdoor thermostat is recommended for each stage
of electric heat after the first stage. Set the outdoor
thermostat(s) progressively lower for each stage.
Refer to heat load of building and unit capacity to
determine the correct outdoor thermostat settings.
> The accessory supplemental heat relay is required
when 2 outdoor thermostats are used. It is auto-
FACTORY WIRING
Fig. 8 — Line Power Connections
8