beautypg.com

Carrier 38HQ User Manual

Page 8

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

CONNECT

GROUND

LEADS

AND

POWER

WIRING

Connect ground leads to the ground lug in

control box for safety. Connect power wiring. See

Fig. 8. Splice compressor section line power leads

to yellow and black pigtails, and outdoor coil power
leads to brown and blue pigtails. Use wire nuts and
tape each connection.

CONNECT

POWER

LEADS

FROM

INDOOR

COMPRESSOR

SECTION

TO

OUTDOOR

COIL thru outdoor disconnect switch. From dis­
connect switch extend leads thru hole provided in
coil basepan (Fig. 1) and into line voltage section
of junction box, Fig. 24. Splice leads to black and

blue pigtails with wire nuts.

SEE

INDOOR

FAN

COIL

AND

ELECTRIC

HEATER

INSTALLATION,

START-UP

AND

SERVICE INSTRUCTIONS for line power wiring
details. All control wiring connections are shown
in this booklet.

CONNECT CONTROL POWER WIRING (24 v)
— Extend wiring thru 7/8-in. grommeted hole in
compressor section top panel (Fig. 2), and to control

wiring terminal board on side of control box. Con­

nect leads to terminal board as shown in Fig. 9.

Extend and connect control wiring from compressor

section to outdoor coil as required. Make splice

connections in low voltage section of coil junction

box.

Use indoor fan coil transformer as 24-v supply for

system. At least a 60-va transformer is recom­
mended.

Carrier

approved

indoor

units

are

equipped with a 60-va transformer. See Indoor

Unit data.

Use Carrier accessory

indoor thermostat with

subbase. Table 4.

START-UP

The

38HQ

Indoor

Section

Compressor

is

equipped with a crankcase heater. It is recom­

mended that heater be energized a minimum of 24
hours before starting unit. To energize heater only,

turn the thermostat to OFF position and close

electrical disconnect to heat pump.

Heat Anticipator Settings for Room Thermo­

stat (HH07AT071) — Set anticipator settings for

room

thermostat

according

to

Table

6.

These

settings may be changed slightly to provide a greater
degree of comfort for a particular installation.

> Table 6 — Thermostat Anticipator Settings

INDOOR

COMPR

SECTION

OUTDOOR

COIL

FIRST-

STAGE

ANTICI­

PATOR

SETTING

INDOOR

UNIT WITH

ELECTRIC

HTR

KW

SECOND-

STAGE

ANTICI­

PATOR

38HQ

HEATER

SETTINGS

(Ampi

40AQ

Fan Coil

5 0

120

940

with

7 5

10.0

25

127

940

40AQ Htrs

12 0
15 0

134

940

Fixed

40FS/28HO,VQ

50

140

960

with 40FQ

Htrs

20 0

146

960

25 0

40QB Fan Coil

with 40QB Htrs.

30 0

75

Accessory Outdoor Thermostat provides adjust­

able outdoor control of accessory electric heater
(used on indoor fan coil). This thermostat makes
contact when a drop in outdoor temperature occurs.

It energizes a stage of electric heat when the outdoor

temperature setting is reached, provided the room

thermostat is on the second stage of heating. One

outdoor thermostat is recommended for each stage
of electric heat after the first stage. Set the outdoor
thermostat(s) progressively lower for each stage.

Refer to heat load of building and unit capacity to

determine the correct outdoor thermostat settings.

> The accessory supplemental heat relay is required

when 2 outdoor thermostats are used. It is auto-

FACTORY WIRING

Fig. 8 — Line Power Connections

8