beautypg.com

Carrier 38HQ User Manual

Page 6

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

REPLACE

THE

ACCURATER™

REFRIG­

ERANT CONTROL PISTON IN THE INDOOR
AND OUTDOOR COIL AS REQUIRED before
connecting refrigerant lines. See Table 3 and the
notes under the table for the pistons used in the
different system combinations. For piston replace­
ment

instructions,

see

AccuRater

Servicing

on

page 16.

CONNECT REFRIGERANT LINES to fittings on
indoor and outdoor sections, Fig. 1,2 and 6. Indoor

compressor section has 2 Compatible Fitting vapor

line connections. Outdoor coils and indoor fan coils
have Compatible Fitting vapor line connection and

liquid line flare connection.

Connect vapor line from outdoor coil to indoor

compressor section, and from compressor section
to indoor fan coil. Section vapor line as required
(Fig. 6). Use correct compressor section vapor line
connection to indoor fan coil and outdoor coil.

Unit Compatible Fitting(s) permits mechanical or

sweat connection as described below.

When using 1-1/8 in. field-supplied vapor line

(38HQ146 Systems^ remove vapor line adapters (4)

shipped in compressor section. Sweat connect 1-1/8
in. end of adapter to each end of vapor lines. Con­
nect 3/4-in. end of adapters to vapor line Com­

patible

Fitting(s)

on

outdoor

coil,

indoor

compressor section and indoor fan coil.

When a 7/8-in. field-supplied vapor line is used

on 38HQ140, 4 field-supplied 3/4-in. to 7/8-in.

vapor line adapters must be provided (not required

if 7/8-in. 38CQ accessory tubing is used).

Flare

and

connect

liquid

line

from

outdoor

coil

to

indoor

fan

coil.

(Do

not

disassemble

AccuRater.) It is not necessary to flare system

liquid

line

if

an

accessory

flare-to-Compatible

Fitting Coupler is used for liquid line connec­

tion. See Accessory Coupler, Fig. 7.

Mechanical

Connection

to

Compatible

Fitting

(Mate one set of connections at a time.)

1. Loosen nut on Compatible Fitting one turn. Do

not remove.

2. Remove plug and be sure O-ring is in the groove

inside the Compatible Fitting.

3. Cut tubing to correct length.

4.

Insert tube into Compatible Fitting until it

bottoms.

5.

Tighten nut until it bottoms on back coupler

flange.

Keep

tube

bottomed

in

Compatible

Fitting while tightening nut.

Fig. 6 — Refrigerant Piping Connections