beautypg.com

Carrier 38HQ User Manual

Page 15

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

6.

From intersect point, project vertically down­

ward to chart suction pressure line. Compare

chart suction pressure to unit suction pressure
(Step 2).

7.

If unit suction pressure is lower than chart

pressure, add refrigerant to system until chart
pressure is reached. If unit suction pressure is

higher than chart pressure, remove refrigerant

until chart pressure is reached.

Unit

Single-Phase

Compressors

that

are

Equipped with a Compressor Start Thermistor

(PTC device) — When supply voltage is within 10%

limit and compressor does not start, check the start
thermistor with an ohmmeter.

If PTC resistance is 0 ohm (open) or higher than

200% of the rating, the device is defective.

Compressor Removal — See Table 8 for com­

pressor information and Fig. 24 for component
location.

Remove refrigerant from system using refrigerant

removal

methods

described

in

Carrier

Standard

Service Techniques Manual, Chapter 1.

Follow safety codes, and wear safety glasses and

work gloves. Have quenching cloth available.

1. Remove unit top cover and front access

wrapper.

2. Remove compressor terminal box cover, dis­

connect and remove compressor power leads.

3. Using a tubing cutter, cut suction and discharge

lines at convenient place near compressor for

easy reassembly to new compressor with copper
slip couplings.

4. Remove crankcase heater from compressor

base.

5.

Remove compressor hold-down bolts. Lift out

compressor.

6.

Carefully unbraze suction and discharge line

piping stubs from compressor. If oil vapor in
piping stubs ignites, use quenching cloth.

7. Braze piping stubs (removed in step 6) on new

compressor.

8. Clean system. Add new liquid line heat pump

filter-drier as described below.

9.

Install new compressor in unit. Braze suction

and discharge lines to compressor piping stubs

(at points where cut, step 3) using field-
supplied copper couplings. Ensure compressor

hold-down bolts are in place. Connect wiring.

10. Evacuate and recharge system.

FILTER-DRIER — Install accessory heat pump

filter-drier (Table 4) in system liquid line when

refrigerant system is opened for service as described
under Compressor Removal. Position drier in liquid
line at convenient location.

Unit Controls and Safety Devices

HIGH-PRESSURE RELIEF VALVE is located in

compressor. Relief valve opens at a pressure differ­
ential of approximately 600 psi between suction
(low side) and discharge (high side) to allow pres­

sure equalization.

INTERNAL

CURRENT

AND

TEMPERATURE

SENSITIVE

OVERLOAD

resets

automatically

when internal compressor motor temperature drops
to a safe level (overloads may require up to 45

minutes to reset). When an internal overload is

suspected

of

being

open,

check

by

using

an

ohmmeter or continuity tester. If necessary, refer

to

Carrier Standard Service Techniques Manual,

Chapter 2, for complete instructions.

LOW-PRESSURE

SWITCH

is

located

in

com­

pressor section on suction line between reversing
valve and accumulator. Provides loss of charge pro­
tection

by

shutting

compressor

off

if

suction

pressure drops below setting. Low-pressure switch

settings are: open, 5 ± 3 psig; close, 20 ± 5 psig.

CRANKCASE HEATER is connected across line

side of contactor and operates continuously.

The purpose of the heater is to keep the crank­

case warm during the off cycle and thus prevent

dilution of the oil with refrigerant. This assures good

lubrication and prevents loss of oil from crankcase

during start-up.

If the electrical disconnect switch to the com­

pressor section has been off for an extended period

of time, the crankcase heater should be energized for

24 hours before starting the compressor.

SYSTEM

MALFUNCTION

WARNING

INDI­

CATOR turns on indoor thermostat light if ther­

mostat calls for heating or cooling and compressor

doesn’t

operate

because;

low-pressure

switch

or

internal line break has functioned; control device

or compressor is not operational. The light turns off
when

compressor

restarts,

indoor

thermostat

is

satisfied or if thermostat is manually turned off,
then on.

15