beautypg.com

Carrier 50LJ008-014 User Manual

Page 7

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Install conduit through side panel openings. Install con­

duit between disconnect and control box. Install power lines
to terminal connections as shown in Fig. 7.

Voltage to compressor terminals during operation must

be within voltage range indicated on unit nameplate (see
Table 2). On 3-phase units, voltages between phases must
be balanced within 2% and the current within 10%. Use the
formula shown in Table 2, Note 2 to determine the % volt­

age imbalance. Operation on improper line voltage or ex­

cessive phase imbalance constitutes abuse and may cause
damage to electrical components. Such operation would in­
validate any applicable Carrier warranty.

FIELD CONTROL WIRING — Install a Carrier-approved
accessory thermostat assembly according to installation in­
structions included with the accessory. Locate thermostat
assembly on a solid wall in the conditioned space to sense

average temperature in accordance with thermostat instal­
lation instructions.

Route thermostat cable or equivalent single leads of col­

ored wire from subbase terminals to low-voltage connec­
tions on unit (shown in Fig. 8) as described in Steps 1-4
below.

NOTE; For wire runs up to 50 ft, use no. 18 AWG (Amer­
ican Wire Gage) insulated wire (35 C minimum). For 50 to
75 ft, use no. 16 AWG insulated wire (35 C minimum).
For over 75 ft, use no. 14 AWG insulated wire (35 C min­

imum). All wire larger than no. 18 AWG cannot be directly
connected to the thermostat and will require a junction box
and splice at the thermostat.

1. If unit is mounted on roof curb and accessory thru-the-

curb service plate connection is used, route wire through
connection plate.

2. Pass control wires through the hole provided on unit (see

connection D, Connection Sizes Table, Fig. 6).

3. Feed wire through the raceway built into the corner post

to the 24-v barrier located on the left side of the control
box. See Fig. 9. The raceway provides the UL-required
clearance between the high- and low-voltage wiring

4. Connect thermostat wires to screw terminals of low-

voltage connector.

HEAT ANTICIPATOR SETTINGS - Set heat anticipator
settings as shown in Table 3.

#

BLK

YEL I

I BLU

TO COMPS

'v'

TB2

I-- 1

BLK

YEL I

I 1

' ! 1

' !

<£>

' '

^

' 1
' '

<§)

' 1

1 1

<§>

ft

TO COMPS

BLU

50LJ008-014. 575-3-60

DISCONNECT

PER NEC

FIELD POWER SUPPLY

! DÌSCONNÌCT I

I______________I

50LJ008-012, 208/230-3-60; 50LJ008-014.460-3-60

LEGEND

50LJ014, 208/230-3-60

DISCONNECT

PER NEC

C
COMP(S)
IFC

NEC

TB

Contactor

Compressor(s)

Indoor (Evaporator) Fan Contactor

National Electrical Code

Terminal Block

Terminal Block Connection

Splice Connection

Field Wiring
Factory Wiring

Fig. 7 — Power Wiring Connections