029 stssl, A.72, Iysei – Carrier 50LJ008-014 User Manual
Page 11: As'i, Iiaas, Mm ms, Mm sm
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
Table 7 — Fan Performance, 50LJ008,009 — Vertical Discharge Units
Bhp
LEGEND
— Brake Horsepower
NOTES:
1
. Boldface
indicates field-supplied drive required
2
indicates field-suppiied motor and drive required.
3 Maximum usabie bhp is 2.4. Extensive motor and electrical test
ing on the Weathermaker® I units ensures that the full horse
power range of the motor can be utilized with confidence Using
your fan motors up to the horsepower ratings shown will not re
sult in nuisance tripping or premature motor failure. Unit warranty
wiil not be affected
Use of field-supplied motor may affect wire sizing Contact your
Carrier representative to verify
Values include losses for filters, unit casing and wet coils.
Motor drive range is 590 to 840 rpm. All other rpms require a
field-supplied drive
Table 8 — Fan Performance, 50LJ012 - Vertical Discharge Units
EXTERNAL STATIC PRESSURE (in. wg)
IRFLOW
(Cfm)
0.2
0.4
0.6
0.8
1.0
1.2
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
3000
532
0.64
605
0.81
670
0.97
725
1.12
778
1 28
825
1.43
3100
544
0.70
616
0.86
680
1.03
735
1 20
787
1.36
835
1 52
3200
557
0.75
628
0.93
690
1 10
746
1.28
796
1.44
844
1 61
3300
570
0.81
639
0.99
700
1 18
757
1.36
805
1.52
854
1.70
3400
583
0.88
651
1.06
711
1 25
767
1 44
815
1 61
863
1.79
3500
596
0.94
663
1.14
721
1.33
711
1.52
826
1.71
871
1 88
3600
609
1.01
674
1.22
732
1 42
787
1.61
836
1.80
880
1 98
3700
622
1.09
686
1.30
744
1 50
797
1.70
847
1 91
890
2.09
3800
635
1.16
698
1 39
755
1.59
808
1.80
857
2.01
901
2 20
3900
649
1.25
710
1 48
767
1.68
818
1 90
867
2.11
912
2.32
4000
662
1.33
722
1.57
778
1 78
829
2.01
878
2 22
4100
675
1.42
734
1.67
790
1.89
839
2.12
888
2.33
4200
689
1.52
746
1 77
801
1 99
851
2 23
mm
4300
702
1.61
759
1.88
813
2 11
862
2.34
90©
■Z.SS:10S®|3
4400
715
1 72
772
1.99
825
2.22
mM
2.7?,
4500
729
1.83
785
2 10
837
2.35
S8&
029
STSSl.
4600
742
1.94
797
2.22
mm ms
89©
a.72:
S40
iysei
4700
756
2 06
810
2.34
as'i
4800
770
2 18
mm
ms
—
4900
783
2.31
mm
SM
—
—
5000
mm
iiaas:
mm
-
~
1012J 2.36
LEGEND
Bhp
— Brake Horsepower
NOTES:
1
Boldface
indicates field-supplied drive required
2.
indicates field-supplied motor and drive required
3. Maximum usable bhp is 2.4. Extensive motor and electrical test
ing on the Weathermaker I units ensures that the full horsepower
range of the motor can be utilized with confidence. Using your
fan motors up to the horsepower ratings shown will not result in
nuisance tripping or premature motor failure Unit warranty will
not be affected.
Use of field-supplied motor may affect wire sizing. Contact your
Carrier representative to
verify.
Values include losses for filters, unit casing and wet coils
Motor drive range is 690 to 935 rpm. All other rpms
require a
field-supplied drive.
11