beautypg.com

Carrier 50CD/CH User Manual

Page 7

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

MANUAL

OUTDOOR

air

damper

assembly

L/NKA6E
ROD SETSCREW

#

a; . •W

LINKAGE ROD

Fig. 7 — Damper Blade Adjustment

Fig. 10 — Control Box Details

m

Fig. 8 — Manual Outdoor Air Damper

HOOD

BASE UNIT

•>

^,r

AIR SCREENS

BASE RAIL

Fig. 9 — Outdoor Air Hood Assembled

to Base Unit (50 Series Shown)

Condenser Air Fan and Motor are factory set.

Refer to Service, Condenser Air Fan Adjustment,

as required.

Condensate Drain — See Fig. 3 and 4 for drain
location. A 7/8-in. ID preformed drain hose is

shipped clamped to the evaporator basepan. At

installation, reroute hose so that it passes thru the
hole in the evaporator basepan and the unit base

rail.

When installed properly, the hose protrudes thru

the base rail about 3in. on the 50CD008. On the

50CH008, hose protrudes thru the side of the base
rail about 1 inch.

Replace clamp over the hose where it passes thru

the basepan. This keeps the hose level. Use a trap at
least 4 in. deep and provide protection for trap
against freeze-up.

Field Power Supply — See Fig. 11 and Table 2.

Unit is factory wired for voltage shown on name­

plate. On 208-volt installations, reconnect all trans­

formers to 208- (200-) volt tap. Refer to unit label

diagrams. Pigtails are provided for field service on
units without electric heat (use factory-supplied

splices or UL-approved copper/aluminum con­

nector). Units with electric heat are provided with
terminal block in single point box.

All field wiring must comply with National Elec­

trical Code and local requirements.

Run power lines thru condenser coil end panel to

terminal connections as shown on unit wiring

diagram and in Fig. 3 and Fig. 4.

Operating voltage to compressor must be within

voltage range indicated on unit nameplate. On 3-

phase Units, voltages between phases must be
balanced within 2% and the current must be bal­

anced within 10%.

Use the following formula to determine the %

voltage unbalance.

% Voltage Unbalance

_ max voltage deviation from average voltage

average voltage