vent air needed and record quantity for vent
adjustment in step 11.

5. Remove jumper plug from base unit receptacle

and discard. Insert economizer plug into recep­
tacle. See Fig. 15.

Steps 6 thru 8 involve releasing and adjusting

indoor damper blades from factory set position.

Fig. 14 — Outdoor Air Hood Details

ECONOMIZER
PLUG

BASE UNIT

RECEPTACLE

OUTDOOR AIR

INLET SCREENS (3)

CLS — Cooling Lockout Switch
EC — Enthalpy Control

OAT. — Outdoor Air Thermostat

Fig. 15 — Economizer Installed in Unit

6. Release indoor blades’ drive linkage by loosen­

ing linkage connector setscrew at indoor crank-
arm on drive shaft. See Fig. 16.

Remove pink wire from economizer damper

motor terminal D and temporarily tape bare
wire end.

Remove violet wire from economizer damper

motor and connect to terminal D on economizer
damper motor. See Fig. 17.

OUTDOOR BLADES (2)

DRIVE

SHAFT

OUTDOOR DRIVE LINKAGE

Fig. 16 — Economizer Details

INDOOR
BLADES (3)

PINK WIRE

VIOLET WIRE

TERMINAL D

Fig. 17 — Economizer Motor Connections

7. Jumper red (base unit 24-v power) and black

(evaporator fan motor) wires in 24-volt control
box compartment. See Fig. 10.

Turn on base unit power to energize evap­
orator fan. The economizer’s outdoor blades

should open completely.

8. Adjust the indoor blades’ drive linkage so that

indoor blades are fully closed. Tighten the

linkage connector setscrew. Turn off base unit

power. Reconnect pink and violet wires to

economizer motor, as shown in Fig. 17.

9. If vent air is required, leave red and black wires

jumpered. If vent air is not needed, remove
jumper between red and black wires.

10. Fasten baffle to left side of damper plate with

round head screws provided. See Fig. 18.

t

10