Table 1 — Physical Data

UNIT SIZE

50CD/CH008

OPERATING WEIGHT (lb)

Unit

730

With Economizer*

790

Roof Curb* — 14 in.

120

COMPRESSOR

No. ...Type

1 — BRE2 Copeland

Oil (oz)

124

REFRIGERANT (Capillary Control)

R-22

Charge (lb)

105

CONDENSER COIL

Copper Tubes, Aluminum Fins

Rows

2

Fins/in.

13 9

Total Face Area (sq ft)

15 6

CONDENSER AIR FAN

Nominal Cfm

4100

No. ...Diameter (in.)

1 22

Motor Hp (1075 Rpm)

1/2 Hp

EVAPORATOR COIL

Copper Tubes, Aluminum Fins

Rows

3

Fins/in.

13 9

Total Face Area (sq ft)

82

EVAPORATOR AIR FAN

Quantity...Size (in )

1 1 2 x 9

Nominal Cfm

3000

Minimum and Maximum Cfm (Standard Motor)

2250 - 3650

(Optional Motor)

2250 - 3750

Rpm Range
Maximum Allowable Rpm

Motor Pulley Pitch Diameter (in.)
Fan Pulley Pitch Diameter (in )
Belt No. ...Type
Speed Change per Full Turn of

652 - 924

924

2 4-3 4

12 7

1 A51

54

Moveable Pulley Flange (Rpm)

Moveable Pulley Maximum Full Turns

from Closed Position

Factory Setting — Full Turns Open

3

Factory Speed Setting (Rpm)

760

Motor Hp (Service Factor) Standard

1 Hp (1 4)

Optional

1 5 Hp (1 3)

HIGH-PRESSURE SWITCH

Cutout (psig)

426 ± 7

Reset (psig)

320 ± 20

LOW-PRESSURE SWITCH (Liquid Line)

Cutout (psig)

27 ± 4

Reset (psig)

67 ± 7

OUTDOOR AIR INLET SCREENS*

Economizer, No . Size (in )

2 19 X 31 X 1/2 — None on 50CH008

RETURN AIR FILTERS* (Type)

Disposable — None on 50CH008

No. ...Size (in.)

2 16 X 20 X 1
2 20 X 20 X 1

»50CD008 only

Accessory Roof Curb (50CD008) — See Fig. 2.

Assemble and install in aeeordance with instruetions
shipped with curb. Install insulation, cant strips,
roofing and flashing as required. Ductwork must

be attached to curb.

Unit gasketing to roof curb is critical for water

integrity. Make sure that gasketing material shipped
with the roof curb has been properly installed as
indicated in Fig. 2.

Roof Mount — Check building codes for weight

distribution requirements. Table 1 shows unit
weight.
Slab Mount (50CH008) — Provide a level con­
crete slab the same width as unit that extends to ends

of base rails only. The slab should be 8 in. thick with
4 in. above grade. Install a gravel apron in front of

outdoor air inlet to prevent grass and foliage from

obstructing airflow. Allow a minimum of 6 in. under
outdoor coil for condensate drainage. In areas

where prolonged sub-freezing temperatures or

heavy snow occur, increase clearance to 12 in. mini­

mum, 18 in. maximum.

Positioning — Position unit to prevent snowdrifts

from blocking condenser coil and outdoor air intake

(50CD008). Provide clearance around and above
unit for airflow, safety and service access.

Do not install unit in an indoor location. Do not

locate unit air inlets near exhaust vents or other
sources of contaminated air.

Although unit is weatherproof, guard against

water from higher level runoff and overhangs.

©