beautypg.com

Carrier 50CD/CH User Manual

Page 12

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

13. Fasten hood top and side plate assembly

(Fig. 9) and eeonomizer to unit with screws
supplied. Before attaching, make sure bottom

of hood assembly is resting on top of unit base
rail.

14. Place knob supplied with accessory economizer

on OAT. See Fig. 20. Set for 3 degrees below
indoor room thermostat setting.

If accessory enthalpy control (EC) (Fig. 20) is

used in lieu of OAT., refer to instructions

shipped with accessory enthalpy control for
installation and adjustment.

15. Connect OAT./EC and CLS per unit label.

See Fig. 21.

Connect 2 economizer wires to each switch

with quick-connects. Unit connecting wires are
shipped taped on outdoor blade. See Fig. 15.

16. Slide outdoor air inlet screens in hood screen

tracks. Secure screens with screen retainer
across hood front. Secure screen retainer with

screw provided. See Fig. 22.

17. Replace upper filter access panel with screws

saved from step 2.

18. Turn base unit power on.

CLS

PINK

-O^Q-

PINK

-i

SEE NOTE

F

RED

_ OAT _

-

BLUE

CLS — Cooling Lockout Switch

EC — Enthalpy Control

OAT. — Outdoor Air Thermostat

NOTE; When Enthalpy Control (EC) is installed, outdoor air thermo­
stat (OAT ) is removed from economizer

Fig. 21 — Wiring Connections for Outdoor

Air Thermostat/or Enthalpy Control

and Cooling Lockout Switch

AIR INLET SCREEN

RETAINER

OUTDOOR AIR

HOOD

BASE UNIT

: *

BASE RAIL

Fig. 22 — Economizer and Outdoor Air Hood

Assembled to Unit

START-UP

Unit Preparation — Make sure unit has been
installed in accordance with installation instruc­
tions and applicable codes.

Compressor Mounting — Compressors are inter­
nally spring mounted. Do not loosen or remove

compressor holddown bolts.

Internal Wiring — Check all electrical connections

in unit control boxes. . .tighten as required.

Refrigerant Service Valves — Eaeh unit system

has 2 Schrader type serviee ports, one on the suetion
line and one on the compressor discharge line. Be

sure that eaps on the ports are tight.

Crankcase Heater(s) are energized as long as there
is power to the unit. Energize heater(s) 24 hours
prior to base unit start-up.

Cooling — To start unit, turn on main power
supply. Set system selector switch to COOL and
fan switch at AUTO. Adjust thermostat to a setting
below room temperature. Compressor starts on
closure of contactor.

Check cooling effects at a setting above room

temperature. Cheek unit charge. Refer to Refrig­
eration Charge in Service section.

Reset thermostat at a position above room tem­

perature. Compressor will shut off.

TO SHUT OFF UNIT — Set system seleetor switch

at OFF position or reset thermostat at a position
above room temperature. Units are equipped with

Cyele-LOC™ proteetion device. Unit shuts down on
any safety trip, and indicator light on thermostat
comes on. Cheek reason for safety trip.

Compressor restart is accomplished by manual

reset at the thermostat by turning the seleetor switch

to OFF and then to ON.

Heating — To start unit, turn on main power

supply. Refer to Crankcase Heaters.

Set thermostat at HEAT and a setting above

room temperature, fan at AUTO.

First stage of thermostat energizes the first-stage

eleetric heater; seeond-stage electric heater elements

if installed. Cheek heating effeets at air supply

grille(s).

TO SHUT OFF UNIT — Set system selector switch

at OFF or set heating selector lever below room

temperature.

Ventilation {Continuous Fan) — Set fan and sys­
tem selector switches at ON and OFF, respectively.

Evaporator air fan operates continuously to provide
constant air circulation.

Economizer Operation {50CD008) — See

pages 9 thru 12 for start-up and checkout proce­
dures. If unit is equipped with modulating out­

door air control (economizer), it should operate as
follows;

COOLING MODE — Evaporator and condenser

fans and compressor energize when there is a call

t

12