beautypg.com

A caution – Carrier 38AH024-034 User Manual

Page 14

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

PRE-START-UP

IMPORTANT: Before beginning Pre-Start-Up or
Start-Up, review Start-Up Checklist at the back of this
book. The Checklist assures proper start-up of a unit
and provides a record of unit condition, application
requirements, system information, and operation at ini­
tial start-up.

A

CAUTION

Do not attempt to start the condensing unit, even
momentarily, until the following steps have been com­
pleted. Compressor damage may result.

System Check

1. Check all air handler(s) and other equipment auxiliary

components. Consult the manufacturer’s instructions re­
garding any other equipment connected to the condens­

ing unit. If unit has field-installed accessories, be sure
all are properly installed and correctly wired. If used,
airflow switch must be properly installed. See Fig. 9
or 10.

2. Backseat (open) compressor suction and discharge valves.

Now close valves one turn to allow refrigerant pressure
to reach test gages.

3. Open liquid line service valves.

4. Check tightness of all electrical connections.
5. Compressor oil level should be visible in sight glass.

Adjust the oil level as required. No oil should be
removed unless the crankcase heater has been ener­
gized for at least 24 hours. See Service section. Oil
Charge on page 18.

6. Be sure unit is properly leak checked, dehydrated, and

charged. See Preliminary Charge, below.

7. Electrical power source must agree with nameplate

rating.

8. Crankcase heater must be firmly locked into compres­

sor crankcase. Be sure crankcase is warm (heater must
be on for 24 hours before starting compressor).

9. Fan motors are 3-phase. Check rotation of fans during

first start-up check. Fan rotation is counterclockwise
as viewed from top of unit. If fan is not turning
counterclockwise, reverse 2 of the power wires.

10. Be sure compressor floats freely on the mounting springs

and that snubber washers can be moved with finger pres­
sure. See Compressor Mounting, page 5, and Fig. 3
for loosening compressor bolts.

Leak Test and Dehydration

— Leak test the entire

refrigerant system using soap bubbles and/or an electric
leak detector. Evacuate and dehydrate entire refrigerant sys­
tem by use of methods described in GTAC II, Module 4,
System Dehydration.

Preliminary Charge

— Refer to GTAC II, Module 5,

Charging, Recovery, Recycling, and Reclamation for charg­
ing methods and procedures. Charge each system with R-22
by the liquid charging method (through liquid service valve)
on the high side. See approximate refrigerant charge in
Table 1A or IB. Charge according to the values in the Charg­

ing Chart, Eig. 11, page 16.

START-UP

Compressor crankcase heaters must be on for 24 hours

before start-up. To energize the crankcase heaters, set the
space thermostat above the ambient so there will be no de­
mand for cooling. Close the field disconnect and turn on
the fan circuit breakers. Leave the compressor circuit break­
ers off/open. The crankcase heaters are now energized.

After the heater has been on for 24 hours, the unit can be

started. If no time has elapsed since the preliminary charge
step has been completed, it is unnecessary to wait the

24-hour period.

Preliminary Checks

1. Ensure that compressor service valves are backseated.

2. Verify that each compressor floats freely on its mount­

ing springs.

3. Check that electric power supply agrees with unit name­

plate data.

4. Verify that compressor crankcase heaters are securely in

place.

5. Check that compressor crankcase heaters have been on

at least 24 hours.

6. Note that compressor oil level is visible in the sight glass.
7. Recheck for leaks using same procedure as previously

outlined in Pre-Start-Up section. Leak Test and De­
hydration, this page.

8. If any leads are detected, evacuate and dehydrate as pre­

viously outlined in Pre-Start-Up section. Leak Test and
Dehydration, this page.

Preliminary Oil Charge

— Each compressor is fac­

tory charged with oil (see Table lA or IB). When oil is
checked at start-up, it may be necessary to add or remove
oil to bring it to the proper level. One recommended oil
level adjustment method is as follows:

ADD OIL — Close suction service valve and pump down
crankcase to 2 psig (14 kPa). (Low-pressure switch must be

jumpered.) Wait a few minutes and repeat until pressure re­

mains steady at 2 psig (14 kPa). Remove oil fill plug above
the bull’s-eye, add oil through plug hole, and replace plug.
Run compressor for 20 minutes and check oil level.

NOTE: Use only Carrier approved compressor oil. Ap­
proved sources are:

Petroleum Specialties Inc..................................... Cryol 150A
Texaco, Inc......................................................Capella WF-32
Witco Chemical Co...............................................Suniso 3GS

Do not use oil that has been drained out, or oil that has
been exposed to atmosphere.

REMOVE OIL — Pump down compressor to 2 psig
(14 kPag). Loosen the Ut-in. (6.4 mm) pipe plug at the com­
pressor base and allow the oil to seep out past the threads
of the plug.

NOTE: The crankcase will be slightly pressurized. Do not
remove the plug, or the entire oil charge will be lost.

Small amounts of oil can be removed through the oil pump

discharge connection while the compressor is running.

Start Unit

— The field disconnect is closed, the fan cir­

cuit breaker is closed and the space thermostats are set above

ambient so that there is no demand for cooling. Only the
crankcase heaters will be energized.

i

14