beautypg.com

Carrier 38AH024-034 User Manual

Page 12

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

LLSV CONTROL SCHEMATIC 124 VI

AFS

— Airflow Switch

LLSV

C

— Contactor, Compressor

LOR

CB

— Circuit Breaker

LPS

CLO

— Compressor Lock-Out

OPS

COM

— Common

PL

COTP

— Compressor Overcurrent Protection

SOLR

CR

— Control Relay

STAT

DISC

— Disconnect

TB

HPS

— High-Pressure Switch

TGD

IPC

— Indoor-Fan Contactor

TRAN

IPR

— Indoor-Fan Relay

U

kcmil

— thousand circular mils

VA

LLS

— Liquid Line Solenoid

VAV

LEGEND

Liquid Line Solenoid Valve
Lock-Out Relay
Low-Pressure Switch
Oil Pressure Switch
Plug Assembly
Solenoid Relay
Thermostat
Terminal Block
Time Guard® Device
Transformer

Unloader (Solenoid)

Volt-Ampere
Variable Air Volume

I I Terminal Block Connection

^—>

Marked Terminal

O

Unmarked Terminal

Unmarked Splice
Field Accessory Wiring
Factory Wiring
Field Control Wiring
Field Power Wiring
Indicates Common Potential;
Does Not Represent Wiring

Factory wiring is in accordance with National Electrical Code (NEC)

(U.S A. Standard) Field modifications or additions must be in com­
pliance with all applicable codes

Wiring for field power supply must be rated 75 C minimum. Use
copper, copper-clad aluminum, or aluminum conductors Maxi­

mum incoming wire size for main terminal block (TB1) is 350 max
kcmil (230 v). All other voltages 2/0 AWG (American Wire Gage)
maximum

Terminal blocks TB2, TB3, and TB4 are for external field control
connections Control connections are to be class 2 wiring.

Field-supplied components connected to TB3 (e.g., LLS1 and
LLS2) cannot exceed 75 va total inductive load at 24 vac, so that

NOTES TO FIG. 9 AND 10

TRAN1 does not become overloaded The air handler auxiliary
motor starter contacts must have a minimum rating of 30 va at
24 vac The airflow switch must have minimum contact rating of

125 va at 24 vac.

5. Replacement of factory wires must be with type 105 C wire or its

equivalent

6. Field-supplied liquid line solenoid valves installed at the evapo­

rator are required on circuits no. 1 and 2 on all units

7.

ModuPanel control is wired for one air handler only Re­

move wire between TB2-2 to TB2-7 for ModuPanel control
applications

Fig. 9 — Typical Wiring Schematic — VAV ModuPaner

One Dual-Circuit Condensing Unit with Air Handler

12