31 | PIR Ready VT76xxW Series-Installation Guide

Dhu set
Dehumidification setpoint
Default is 50 % RH

Used only if dehumidification sequence is enabled:

Range is: 30-95% RH

DHumiLCK
Dehumidification lockout
Default value:
Restrict

Enables, restricts or disables the dehumidification sequence.

Dhu Disa: Dehumidification disabled

Restrict: will restrict the dehumidification process based on

the following:

-

System mode = Needs to be Cool or Auto ( currently

operating in cooling only )

-

Low ambient room temperature protection enabled

Dhu Enab: will not restrict the dehumidification process:

-

System mode = Needs to be Cool, Heat or Auto

There is no ambient room temperature protection enabled

Dhu OALK

Dehumidification outside air

temperature lockout

Default value = 32°F (0°C)

Outside air temperature under which the dehumidification

sequence is disabled.

Only valid if an outdoor air sensor is connected at the

Terminal Equipment Controller or a network value is

transmitted to the Terminal Equipment Controller.

From

–40°F up to 122°F (-40°C to 50°C)

DehuHyst
Dehumidification
Hysteresys
Default = 5 % RH

Humidity control hysteresis. Used only if dehumidification
sequence is enabled:
Range is: 2 to 20% RH

MS dis

Display mixed air
temperature

Economizer model only,
only if sensor is installed

Used as diagnostic / service help to troubleshoot and
diagnose economizer operation.