13 | PIR Ready VT76xxW Series-Installation Guide


Frost ON

Indicates that the heating is energized by the low limit frost protection room
temperature setpoint 5.6 °C ( 42 °F )

SetClock

Indicates that the clock needs to be reset. There has been a power failure
which has lasted longer than 6 hours

Service

Indicates that there is a service alarm as per one of the configurable digital
input ( DI1 or DI2 )

Filter

Indicates that the filters are dirty as per one of the configurable digital input (
DI1 or DI2 )

Fan lock

Indicates that the heating and cooling action are locked out due to a defective
fan operation

Three status LEDs on the Terminal Equipment Controller cover are used to indicate the
status of the fan, a call for heat, or a call for cooling.

When any of the fan is ON, the FAN LED will illuminate

When heating is ON, the HEAT LED will illuminate

When cooling is ON, the COOL LED will illuminate


LED

OPERATION

HEATPUMP

MODELS

Fan LED on

When G Fan terminal

operates

Heating LED

on

When Y1 terminal

operates in heating

mode

Cooling LED

on

When Y1 terminal

operates in cooling

mode

U

SER

I

NTERFACE

User configuring instructions menu


The VT7600 series of Terminal Equipment
Controller feature an intuitive, menu-driven, back-lit
LCD display that walks users through the
configuring steps, making the configuring process
extremely simple. This menu is typically accessed
by the user to set the parameters such as
temperature and time events, system mode, fan
mode, etc.

It is possible to bring up the user menu at any time by depressing the MENU key. The
status display automatically resumes after exiting the user-configuring menu.