17 | PIR Ready VT76xxW Series-Installation Guide

Local changes to the heating or cooling setpoints made by the user directly using the up
or down arrow are temporary.
They will remain effective for the duration specified by ToccTime.
Setpoints will revert back to their default value after internal timer ToccTime expires.
If a permanent change to the setpoints is required, use the Temperat set ? menu

D) System mode setting

Sys mode
set Y/N

This menu is accessed to set system mode operation

Use ▲▼ to set value, Yes key to confirm

Sys mode

auto

Automatic mode
Automatic changeover mode between heating and cooling operation

Sys mode

cooling

Cooling mode
Cooling operation mode only

Sys mode

heating

Heating mode
Heating operation mode only

Sys mode

off

Off mode Normal cooling or heating operation disabled
If enabled in installer parameters, only the automatic heating frost protection
at 50 °F ( 10 °C ) is enabled


E) Fan mode setting

Fan mode
set Y/N

This section of the menu is permits the setting of the fan mode operation.
Use ▲▼ to set value, Yes key to confirm

Fan mode

On

On fan mode
Fan is on continuously, even when system mode is OFF.

Fan mode

Auto

Automatic fan mode
Fan cycles on a call for heating or cooling for both occupied & unoccupied
periods.

Fan mode

Smart

Smart fan mode
During occupied periods, fan is on continuously. In unoccupied mode, fan
cycles on a call for heating or cooling.
This selection is available on all models with a communication module, on
all stand-alone (Network Ready) scheduling models or if DI1 or DI2 is set
to RemNSB on stand-alone non-scheduling models.