Ex. #1 Four event retail establishment schedule

Event

Period 1 -

Event 1

Period 1 -

Event 2

Period 2 -

Event 3

Period 2 -

Event 4

Setpoint

Occupied

Unoccupied

Occupied

Unoccupied

Cool

Heat

Cool

Heat

Cool

Heat

Cool

Heat

Daily

72°F

70°F

80°F

62°F

72°F

70 °F

80°F

62 °F

Occupancy

Monday

7.00 AM

5.00 PM

12.00 PM *

12.00 PM *

Day time only

Tuesday

7.00 AM

5.00 PM

12.00 PM *

12.00 PM *

Day time only

Wednesday

7.00 AM

5.00 PM

12.00 PM *

12.00 PM *

Day time only

Thursday

7.00 AM

5.00 PM

7.00 PM

10.30 PM

Day/evening

time only

Friday

7.00 AM

5.00 PM

7.00 PM

10.30 PM

Day/evening

time only

Saturday

12.00 PM *

12.00 PM *

12.00 PM *

12.00 PM *

Unoccupied

Sunday

12.00 PM *

12.00 PM *

12.00 PM *

12.00 PM *

Unoccupied

* Scheduling events to the same time will cancel the last period and leave the Terminal
Equipment Controller in unoccupied mode


Ex. #2 Residential

Event

Period 1 -

Event 1

Period 1 -

Event 2

Period 2 -

Event 3

Period 2 -

Event 4

Setpoint

Occupied

Unoccupied

Occupied

Unoccupied

Cool

Heat

Cool

Heat

Cool

Heat

Cool

Heat

Daily

72°F

70°F

80°F

62°F

72°F

70°F

80°F

62°F

Occupancy

Monday

6:00 AM

8:00 AM

4:00 PM

10:00 PM

Day/evening

time only

Tuesday

6:00 AM

8:00 AM

4:00 PM

10:00 PM

Day/evening

time only

Wednesday

6:00 AM

8:00 AM

4:00 PM

10:00 PM

Day/evening

time only

Thursday

6:00 AM

8:00 AM

4:00 PM

10:00 PM

Day/evening

time only

Friday

6:00 AM

8:00 AM

4:00 PM

11:30 PM

Day/evening

time only

Saturday

8:00 AM *

8:00 AM *

8:00 AM *

11:59 PM *

Day time

only

Sunday

12:00 AM *

12:00 AM *

12:00 AM *

11:59 PM *

Occupied all

day

* Scheduling consecutive events to the same time will cause the Terminal Equipment

Controller to choose the last event as the time at which it will set its schedule. In the above
example for Saturday, the Terminal Equipment Controller will control to the occupied set
point from 8:00 AM until 11:59 PM. Since it is desired to be in occupied mode throughout
the night, then it is necessary to schedule the first event on Sunday at 12:00 AM. The
Terminal Equipment Controller will force a one minute unoccupied period for a one minute
period (between 11:59 PM and 12:00 AM on Saturday).