26 | PIR Ready VT76xxW Series-Installation Guide

lockout Keypad lockout levels

Default value = 0 No lock

0 = No lock
1 = Low level
2 = High level

USER KEY FUNCTIONS

LEVEL

R

e

s

u

me

/

O

v

e

rr

id

e

s

c

h

e

d

u

li

n

g

P

e

rma

n

e

n

t

O

c

c

u

p

ie

d

a

n

d

U

n

o

c

c

u

p

ie

d

S

e

tp

o

in

ts

T

e

mp

o

ra

ry

s

e

tp

o

in

ts

u

s

in

g

a

rr

o

w

s

S

y

s

te

m mo

d

e

s

e

tt

in

g

F

a

n

mo

d

e

s

e

tt

in

g

S

c

h

e

d

u

le

s

s

e

tt

in

g

C

lo

c

k

s

e

tt

in

g

P

e

rma

n

e

n

t

h

o

ld

0

1

2

pwr del

Power-up delay

Default value = 10 seconds

On initial power up of the Terminal Equipment Controller
(each time 24 Vac power supply is removed & re-applied)
there is a delay before any operation is authorized (fan,
cooling or heating). This can be used to sequence start up
multiple units / Terminal Equipment Controller in one
location.

10 to 120 seconds

Frost pr
Frost protection enabled
Default value = Off

Off: no room frost protection
On: room frost protection enabled in all system mode at:
42 °F ( 5.6 °C )
Frost protection is enabled even in system Off mode
Off or On

heat max
Maximum heating setpoint
limit
Default value = 90 °F ( 32 °C )

Maximum occupied & unoccupied heating setpoint
adjustment. Heating setpoint range is:
40 to 90 °F ( 4.5 to 32.0 °C )

cool min
Minimum cooling setpoint limit
Default value = 54 °F ( 12 °C )

Minimum occupied & unoccupied cooling setpoint
adjustment. Cooling setpoint range is:
54 to 100 °F ( 12.0 to 37.5 °C )