24 | PIR Ready VT76xxW Series-Installation Guide

Channel
Channel selection
Default value = 10
Range is: 10 to 26

Conditional parameter to Wireless models
(VT76xxW5x00W)


This parameter will only appear when a wireless
network adapter is present. If the Terminal Equipment
Controller is installed as a stand-alone

(Network

Ready)

unit or with a

BACnet™ or Echelon™ adapter,

this parameter will not be used or displayed

This parameter (Channel) is used to link specific
Terminal Equipment Controllers to specific Viconics
wireless gateway(s) (VWG) For every Terminal
Equipment Controller reporting to a gateway
(maximum of 30 Terminal Equipment Controllers per
gateway), be sure you set the SAME channel value
both at the gateway and the Terminal Equipment
Controller(s).

Viconics recommends using only the usage of
channels 15 and 25 only.

The default value of 10 is NOT a valid channel. The
valid range of available channel is from 11 to 26

Get From
Terminal Equipment Controller
Get From another device
configuration utility
Default value = 0
Range is: 0 to 254

Conditional parameter to Wireless models
VT76xxW5x00W

Entering a MAC address enables an automatic routine
that automatically fetches all the required configuration
properties of the current device from another already
configured device an copies the same required
configured property values.
If a value other than the default value of 255 is entered,
user will then be prompted to exit the Configuration
Menu thus leaving all other parameter configuration to
be copied from the referenced Terminal Equipment
Controller MAC address.

Ex.: If you are currently configuring MAC12 and the
settings matches exactly the settings of ZN MAC5,
then enter 5 as the current parameter value.

If the process is successful and all required
configuration properties have been copied, the
value will revert back to 255

If the process is NOT successful and all required
configuration properties have NOT been copied
( either the reference device is NOT the same
model number or is offline or does not exists ) the
value will revert back to 254 to indicate the failure
of the process

Leaving the Get From parameter to 255 means that
every configuration parameters will be set
manually.