CHS Series

Installation and Operation Instructions │

Slant Fin Corp.

77

Table 15-4 Alert Codes

Code

Description

100

CH modulation range (max minus min) was too small (< 4% or 40 RPM)

101

DHW max modulation rate was invalid, % vs. RPM

102

DHW max modulation rate was > absolute max rate

103

DHW modulation range (max minus min) was too small (< 4% or 40 RPM)

104

Min modulation rate was < absolute min rate

105

Min modulation rate was invalid, % vs. RPM

106

Manual rate was invalid, % vs. RPM

107

Slow start enabled, but forced rate was invalid

108

Analog output hysteresis was invalid

109

Analog modulation output type was invalid

110

IAS open rate differential was invalid

111

IAS open step rate was invalid

112

Mix max modulation rate was invalid, % vs. RPM

113

Mix max modulation rate was > absolute max or < absolute min rates

114

Mix modulation range (max minus min) was too small (< 4% or 40 RPM)

115

Fan was limited to its minimum duty cycle

116

Manual rate was > CH max modulation rate

117

Manual rate was > DHW max modulation rate

118

Manual rate was < min modulation rate

119

Manual rate in Standby was > absolute max rate

120

Modulation commanded rate was > CH max modulation rate

121

Modulation commanded rate was > DHW max modulation rate

122

Modulation commanded rate was < min modulation rate

123

Modulation rate was limited due to outlet limit

124

Modulation rate was limited due to Delta-T limit

125

Modulation rate was limited due to stack limit

126

Modulation rate was limited due to anti-condensation

127

Fan Speed out of range in RUN

128

Modulation rate was limited due to IAS was open

129

Slow start ramp setting of zero will result in no modulation rate change

130

No forced rate was configured for slow start ramp

131

CH demand source was invalid

132

CH P-gain was invalid

133

CH I-gain was invalid

134

CH D-gain was invalid

135

CH OFF hysteresis was invalid

136

CH ON hysteresis was invalid

137

CH sensor type was invalid

138

CH hysteresis step time was invalid

139

CH remote control parameter was invalid

140

CH ODR not allowed with remote control

146

CH control was suspended due to fault

147

CH header temperature was invalid

148

CH outlet temperature was invalid

149

CH steam pressure was invalid

151

Minimum water temperature parameter was greater than setpoint

152

Minimum water temperature parameter was greater than time of day setpoint

155

CH modulation rate source parameter was invalid

157

DHW demand source was invalid